2007-06-23 19:35:48 | *** UNSAT*** |
| |
| ** PLEASE KNOW AS PLANS WERE NOT SUBMITTED WITH ALL |
| COMPLETED INFORMATION FOR CODE COMPLIANCE REVIEW THERE |
| MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| NOT MADE BY OTHER TRADE(S). |
| |
| 3) NOTE PLEASE SEE THE PLANS MAY NOT BE DONE BY A |
| *DESIGNER* WHO IS NOT LICENSED UNDER FS 481 OR 471. |
| PLEASE SEE THE STATEMENT FROM THE ENGINEER DOES NOT |
| COVER THE DESIGNER AS SHOWN ON TITLE BLOCKS PER THE |
| LAWS UNDER THE FLORIDA STATUTES. IF THERE ARE ANY |
| FURTHER QUESTIONS ON THIS PLEASE CONTACT THE STATE |
| LEGAL COUNSEL TO THE BOARD OF ARCHITECTS AS WELL AS THE |
| FLORIDA BOARD OF ENGINEERS. |
| ** THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER |
| OR NOT COMMENT IS MADE BY OTHER TRADE(S). |
| |
| 4) NOTE: PLEASE SEE THE SCOPE OF WORK IS UNCLEAR AS THE |
| TITLE BLOCKS AND LOCATIONS ON PLANS INDICATE THIS AS A |
| RESIDENCE YET THE PLANS AND LOCATION ARE ALSO |
| COMMERCIAL STORES. |
| PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR CHANGE IN |
| OCCUPANCY, PLEASE SUBMIT ELECTRICAL PLANS AND SHOW ALL |
| NEW AND EXISTING WHICH ALREADY COMPLIES OR WILL COMPLY |
| WITH THE CODES ABOVE. |
| PLEASE SEE FBC ADMIN SECTION 106.1, 106.3.5.1.2, 106.2 |
| |
| 5) NOTE: PLEASE SEE NEC , 215.3, 215.5, 230.70, 230.71, |
| 230.76, 230.79, 240.4, 310.16, 408.4, 600.5, 220.12, |
| 220.14, 220.42, 220.44, ETC. |
| |
| 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS AS |
| LIGHTING INFORMATION NEEDS TO COMPLY WITH THE ENERGY |
| CODE. |
| 13-415.1.AB.1.1, 13-415.1.C, 13-415.2 ETC. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |