Date Text
2007-06-23 19:35:48*** UNSAT***
  
 ** PLEASE KNOW AS PLANS WERE NOT SUBMITTED WITH ALL
 COMPLETED INFORMATION FOR CODE COMPLIANCE REVIEW THERE
 MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE PLEASE SEE THE PLANS MAY NOT BE DONE BY A
 *DESIGNER* WHO IS NOT LICENSED UNDER FS 481 OR 471.
 PLEASE SEE THE STATEMENT FROM THE ENGINEER DOES NOT
 COVER THE DESIGNER AS SHOWN ON TITLE BLOCKS PER THE
 LAWS UNDER THE FLORIDA STATUTES. IF THERE ARE ANY
 FURTHER QUESTIONS ON THIS PLEASE CONTACT THE STATE
 LEGAL COUNSEL TO THE BOARD OF ARCHITECTS AS WELL AS THE
 FLORIDA BOARD OF ENGINEERS.
 ** THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 4) NOTE: PLEASE SEE THE SCOPE OF WORK IS UNCLEAR AS THE
 TITLE BLOCKS AND LOCATIONS ON PLANS INDICATE THIS AS A
 RESIDENCE YET THE PLANS AND LOCATION ARE ALSO
 COMMERCIAL STORES.
 PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR CHANGE IN
 OCCUPANCY, PLEASE SUBMIT ELECTRICAL PLANS AND SHOW ALL
 NEW AND EXISTING WHICH ALREADY COMPLIES OR WILL COMPLY
 WITH THE CODES ABOVE.
 PLEASE SEE FBC ADMIN SECTION 106.1, 106.3.5.1.2, 106.2
  
 5) NOTE: PLEASE SEE NEC , 215.3, 215.5, 230.70, 230.71,
 230.76, 230.79, 240.4, 310.16, 408.4, 600.5, 220.12,
 220.14, 220.42, 220.44, ETC.
  
 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS AS
 LIGHTING INFORMATION NEEDS TO COMPLY WITH THE ENERGY
 CODE.
 13-415.1.AB.1.1, 13-415.1.C, 13-415.2 ETC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  