2008-06-10 12:28:13** DENIED**
  
 433 NORTHWOOD
  
 1) NOTE: PLEASE PROVIDE ELEVATION DRAWING FOR
 ELECTRICAL SERVICE DROP AND RISER.
 PLEASE SEE THE ELECTRICAL PLANS SHOW THE SERVICE AT THE
 REAR OF BUILDING YET THE SHEET 1 SHOWS AN ELECTRICAL
 SERVICE OVER HEAD DROP TO THE SIDE OF THIS BUILDING.
 PLEASE KNOW THAT IF THIS EXISTING OVER HEAD SERVICE
 DROP CROSSES OVERTHIS BUILDING TO FEED ANOTHER OR IF
 THIS SERVICE DROP AS SHOWN GOES OVER ANY ROOF OR
 PARKING LOT AREAS THE MINIMUM CLEARANCES PER 230.24
  
 ** THIS COMMENT IS ALSO ON PERMIT FOR 435 AS THE
 ELECTRICAL SERVICE DROP LOCATION APPEARS ON PLANS FOR
 OTHER BUILDING TO FEED THIS BUILDING.
  
 2) NOTE: PLEASE PROVIDE ENERGY CALCULATIONS PER
 13-400.0, 13-101.1, .1.1,.1.2,.1.3 AND .1.4.
  
 3) NOTE: PLEASE VERIFY NOTE ONSHEET #1 WHICH MENTIONS
 NO ELECTRICAL OR PLUMBING IN SCOPE OF WORK BASED ON
 PLANS SUBMITTED THERE IS CLEARLY SHOW ELECTRICAL.
 PLEASE SEE NOTES WITH RESPECT TO MINIMUM TOILET ROOM
 FACILITIES AS THESE WILL AFFECT ELECTRICAL PLANS FOR
 LIGHTING, LAYOUTS ETC.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE CONTROLS
 AS REQUIRED PER NOTE #3 ABOVE.
  
 5) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS PER
 13-415.1.ABC.1.4.
  
 ** IT IS IMPORTANT TO UNDERSTAND AS THERE ARE ITEMS NOT
 IN DESIGN YET AT THIS TIME OR SHOWN ON PLANS, NEW
 COMMENTS MAY BE GENERATE WHICH CAN NOT POSSIBLY BE MADE
 AT THIS TIME. REVIEWS ARE DONE BASED ON PLANS
 SUBMITTED.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved