Date |
Text |
2008-02-04 10:05:48 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK DELETED |
| |
| 5. SHT 7 OF 9 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE BEING |
| DRAINED BY EACH ROOF DRAIN AS WELL AS 1/2 AREA OF ALL |
| VERTICAL WALLS INCLUDING PARAPETS IN THE CALCULATIONS. |
| SHOW THE LOCATION OF THE PRIMARY AND SECONDARY ROOF |
| DRAINS AS WELL AS A DETAIL FOR THE PRIMARY AND |
| SECONDARY ROOF DRAINS. SECTIONS 106.1.1 & 106.1.2. |
| ****NO RESPONSE, BUT THE WALL SECTIONS INDICATE THAT |
| THE ROOF DRAINAGE WILL BE DRAINED OFF ONE END OF THE |
| BUILDING. SECONDARY ROOF DRAINS ARE NOT REQUIRED, BUT |
| THE CALCULATIONS FOR THE SQUARE FOOTAGE OF THE ROOF |
| PLUS THE VERTICAL CONTRIBUTION OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS REQUESTED IN THE PREVIOUS REVIEW |
| HAVE NOT BEEN SUBMITTED. (PLEASE SEE COMMENT 1B). |
| |
| 6. OK SHELL |
| 7. OK SHELL |
| 8. OK SHELL |
| |
| **********NEW COMMENT********** |
| |
| 1B. 1503.6 PROTECTION AGAINST DECAY AND TERMITES. |
| CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. |
| INDICATE THE SIZE OF THE GUTTERS AND THE DOWNSPOUTS AND |
| SHOW THE SLOPE OF THE GUTTER PER TABLE 1106.6. INDICATE |
| THE HIGH POINT OF THE SLOPE. |
| |
| REVIEW BY KEN STEVENS |