Plan Review Notes
Plan Review Notes For Permit 07050950
Permit Number 07050950
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-02-04 12:58:41****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 04.NFPA 101 - 2003 EDITION SHALL BE REFERENCED.
  
 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 06.CONSTRUCTION/DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OF HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING
 STREETS, ALLEYS, FIRE LANES.
  
 07.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 08.THERE ARE TWO SUBMITTED PLAN SETS FOR BOTH 433 AND
 435 AS NUMERICAL ADDRESSES IN THE TITLE BLOCK. PLEASE
 EXPLAIN
  
 09.SHOW THE NUMERICAL ADDRESS ON THE NEW FRONT
 ELEVATION VISIBLE FROM NORTHWOOD ROAD.. AS PER WEST
 PALM BEACH CODE, THESE NUMBERS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 10.SHOW THE ADDRESS NUMBER ON THE NEW REAR ELEVATION
 SO THAT THE SPACE IS DISTINGUISHALBE FROM OTHER UNIT
 SPACES.AS PER WEST PALM BEACH CODE, THESE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 12.SHOW LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS,
 AND FIRE EXTINGUISHERS FOR THE NEW FLOOR PLAN.
  
 13.INDICATE IF THE BUILDING IS EQUIPPED WITH A FIRE
 SPRINKLER AND/OR A FIRE ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722