2008-01-14 11:13:26*** DENIED 2ND REVIEW ***
  
 ** PLANS ARE ONLY NOW BEING SUBMITTED FOR ELECTRICAL
 SCOPE.
  
 1) NOTE: PLEASE SEE APPLIED LOCATION IS 433 NORTHWOOD
 WHICH IS LEGALLY A SEPARATE BUILDING YET PLANS SHOW
 LOCATION OF SCOPE BEING 435 NORTHWOOD.
 PERMIT APPLICATION ALSO SHOWS SCOPE OF WORK TO BE DONE
 ON BOTH BUILDINGS. AS THESE ARE BOTH CONSIDERED
 SEPARATE BUILDINGS PLANS, PERMIT APPLICATION ETC NEEDS
 TO BE COORDINATED.
 PERMIT APPLICATION AND INFORMATION HAS BEEN SENT TO THE
 ADDRESSING REVIEWER FOR DETERMINATION OF THE CORRECT
 LOCATION. THIS WILL ALSO BE CONFIRMED WITH THE BUILDING
 REVIEWER.
  
  
 2) NOTE: PLEASE SEE THE SERVICE RISER AS SHOWN CAN NOT
 BE PERMITTED. THE PLANS INDICATE TWO BUILDINGS AND EACH
 ON SEPARATE PROPERTIES.
 MAY NOT HAVE A SERVICE ON ONE PROPERTY FEEDING A
 SEPARATE LEGAL PROPERTY.
 PLEASE SEE THE MAINS AS SHOWN ARE NOT GROUPED. 230.70,
 230.71, 230.72
 PLEASE KNOW THE SERVICE WILL BE REQUIRED TO BE REVISED
 ONCE FINAL DETERMINATION ON THE BUILDING(S) HAS TAKEN
 PLACE.
  
 3) NOTE: PLEASE SEE MISSING LOADS FIGURED FOR SHOW
 WINDOWS PER 220.43 LOAD ALLOWANCES.
 PLEASE KNOW IF THIS IS GOING TO BE A BUILD OUT FOR
 RETAIL, THE RECEPTACLES IN SHOW WINDOW WILL BE REQUIRED
 TO BE INSTALLED AT THIS TIME.
  
 4) NOTE: PLEASE SEE MISSING MINIMUM LOADS FOR *FUTURE*
 SIGN CIRCUIT PER 600.5. (1200VA MIN)
  
 5) NOTE: PLEASE KNOW ONCE THE FINAL SERVICE HAS BEEN
 DETERMINED; PLEASE PROVIDE THE AIC RATINGS FOR ALL
 EQUIPMENT/ MAINS. FOR EXAMPLE, AIC RATING IS SHOWN FOR
 ONE MAIN WHICH IS THE MAIN BREAKER PANEL BUT NOT FOR
 THE MAIN DISCONNECT.
 THIS NOTE WILL REMAIN AS THE SERVICE AS SHOWN WILL
 CHANGE.
 110.9
  
 6) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT DESIGN
 CODES ARE STATED ON PLANS. (ELECTRICAL )
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 8) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR INTERIOR AND EXTERIOR PER 13-415.2,
 13-415.2.ABC.1.3.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]