2008-01-14 11:13:26 | *** DENIED 2ND REVIEW *** |
| |
| ** PLANS ARE ONLY NOW BEING SUBMITTED FOR ELECTRICAL |
| SCOPE. |
| |
| 1) NOTE: PLEASE SEE APPLIED LOCATION IS 433 NORTHWOOD |
| WHICH IS LEGALLY A SEPARATE BUILDING YET PLANS SHOW |
| LOCATION OF SCOPE BEING 435 NORTHWOOD. |
| PERMIT APPLICATION ALSO SHOWS SCOPE OF WORK TO BE DONE |
| ON BOTH BUILDINGS. AS THESE ARE BOTH CONSIDERED |
| SEPARATE BUILDINGS PLANS, PERMIT APPLICATION ETC NEEDS |
| TO BE COORDINATED. |
| PERMIT APPLICATION AND INFORMATION HAS BEEN SENT TO THE |
| ADDRESSING REVIEWER FOR DETERMINATION OF THE CORRECT |
| LOCATION. THIS WILL ALSO BE CONFIRMED WITH THE BUILDING |
| REVIEWER. |
| |
| |
| 2) NOTE: PLEASE SEE THE SERVICE RISER AS SHOWN CAN NOT |
| BE PERMITTED. THE PLANS INDICATE TWO BUILDINGS AND EACH |
| ON SEPARATE PROPERTIES. |
| MAY NOT HAVE A SERVICE ON ONE PROPERTY FEEDING A |
| SEPARATE LEGAL PROPERTY. |
| PLEASE SEE THE MAINS AS SHOWN ARE NOT GROUPED. 230.70, |
| 230.71, 230.72 |
| PLEASE KNOW THE SERVICE WILL BE REQUIRED TO BE REVISED |
| ONCE FINAL DETERMINATION ON THE BUILDING(S) HAS TAKEN |
| PLACE. |
| |
| 3) NOTE: PLEASE SEE MISSING LOADS FIGURED FOR SHOW |
| WINDOWS PER 220.43 LOAD ALLOWANCES. |
| PLEASE KNOW IF THIS IS GOING TO BE A BUILD OUT FOR |
| RETAIL, THE RECEPTACLES IN SHOW WINDOW WILL BE REQUIRED |
| TO BE INSTALLED AT THIS TIME. |
| |
| 4) NOTE: PLEASE SEE MISSING MINIMUM LOADS FOR *FUTURE* |
| SIGN CIRCUIT PER 600.5. (1200VA MIN) |
| |
| 5) NOTE: PLEASE KNOW ONCE THE FINAL SERVICE HAS BEEN |
| DETERMINED; PLEASE PROVIDE THE AIC RATINGS FOR ALL |
| EQUIPMENT/ MAINS. FOR EXAMPLE, AIC RATING IS SHOWN FOR |
| ONE MAIN WHICH IS THE MAIN BREAKER PANEL BUT NOT FOR |
| THE MAIN DISCONNECT. |
| THIS NOTE WILL REMAIN AS THE SERVICE AS SHOWN WILL |
| CHANGE. |
| 110.9 |
| |
| 6) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT DESIGN |
| CODES ARE STATED ON PLANS. (ELECTRICAL ) |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| |
| 8) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS FOR INTERIOR AND EXTERIOR PER 13-415.2, |
| 13-415.2.ABC.1.3. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |