Plan Review Notes
Plan Review Notes For Permit 07050947
Permit Number 07050947
Review Stop E
Sequence Number 3
Notes
Date Text
2009-02-02 14:09:56** DENIED **
  
  
 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2,
 13-400.3.B, 13-400.2.A.2,
 PLANS SHOW METHOD *C* FROM TABLE, YET SEPARATE METHOD
 *B* ARE ALSO SUBMITTED.
 PLEASE SEE 13-415.2.ABC.1 WHICH DOES NOT PERMIT
 DIFFERENT METHODS. PLEASE SEE COMMENTS FROM OTHER
 TRADES WITH RESPECT TO ITEMS SHOWN ON THE IDR WHICH MAY
 OR MAY NOT BE PART OF THE PLANS. IS THE CEILING GOING
 TO BE INSTALLED? IF NOT WHAT FIXTURES ARE GOING TO BE
 INSTALLED ON WHAT TYPE OF CEILING?
 PLEASE BE SURE TO PLACE SPECIFIC FIXTURE INFORMATION.
 STATING A FIXTURE WITH 2-32W BULBS DOES NOT GIVEN
 INFORMATION ON EFFICIENCY RATING OF BALLAST WHICH IS
 WHAT NEEDS TO BE USED FOR THE ACTUAL WATTAGE IN
 CALCULATIONS. THE VA TO BE USED ON ALL CALCULATIONS ARE
 BASED ON FIXTURE RATING NOT BULB WATTAGES. THIS IS ALSO
 FOR EXTERIOR LIGHTING FIXTURES. PLEASE SEE
 13-415.2.ABC.1.1 AS NOTED ABOVE FOR ACTUAL VA RATINGS
 TO BE USED DEPENDING ON THE TYPE OF
 FIXTURES.13-415.2.ABC.1.3 (EXTERIOR)
  
 2) NOTE: FEE BALANCE FOR EXTENDING PERMIT AND RESUB
 FEES WERE NOT PAID. BALANCE OF FEES IS DUE AT THIS
 TIME. PLANS WILL BE PLACED ON HOLD.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  