Plan Review Notes
Plan Review Notes For Permit 07050947
Permit Number 07050947
Review Stop B
Sequence Number 3
Notes
Date Text
2008-06-04 13:04:33435 NORTHWOOD RD, LOT 29 07050950
  
 BUILDING PLAN REVIEW
 PERMIT: 07050950
 ADD: 433 NORTHWOOD RD
 CONT: KDN CONSTRUCTION SERVICES, LLC
 TEL: (561)662-1002
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)COMPLIED.
  
 2) FL.S. S. 713.13 NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE FL
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4-6)COMPLIED.
  
 7) 2ND REQUEST,SHEET 4 INDICATES TWO SEPARATE UNITS
 LOT 28 & 29, WITH A COMMON WALL. THIS IS A SHARED
 BEARING WALL OR FIRE WALL BETWEEN TWO LOTS OR
 PROPERTIES REQUIRING RATINGS OF WALL AND ROOFDECKING
 . 705.1 WHERE A FIRE WALL ALSO SEPARATES GROUPS THAT
 ARE REQUIRED TO BE SEPARATED BY A FIRE BARRIER WALL,
 THE MOST RESTRICTIVE REQUIREMENTS OF EACH SEPARATION
 SHALL APPLY. FIRE WALLS LOCATED ON LOT LINES SHALL ALSO
 COMPLY WITH SECTION 503.2 . SUCH FIRE WALLS (PARTY
 WALLS) SHALL PROVIDE A 4-HOUR FIRE-RESISTANCE RATING
 AND SHALL BE CONSTRUCTED WITHOUT OPENINGS.
  
 8) 2ND REQUEST, FIRE WALLS OR PARTY WALLS,
 REQUIREMENTS: 705.5 HORIZONTAL CONTINUITY.
 FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO
 EXTERIOR WALL AND SHALL EXTEND AT LEAST 18 INCHES (457
 MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS.
 EXCEPTIONS:
 1.FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE INTERIOR SURFACE OF COMBUSTIBLE EXTERIOR SHEATHING
 OR SIDING PROVIDED THE EXTERIOR WALL HAS A
 FIRE-RESISTANCE RATING OF AT LEAST 1 HOUR FOR A
 HORIZONTAL DISTANCE OF AT LEAST 4 FEET (1220 MM) ON
 BOTH SIDES OF THE FIRE WALL . OPENINGS WITHIN SUCH
 EXTERIOR WALLS SHALL BE PROTECTED BY FIRE ASSEMBLIES
 HAVING A FIRE PROTECTION RATING OF NOT LESS THAN ?
 HOUR.
 2.FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR
 SHEATHING, EXTERIOR SIDING OR OTHER NONCOMBUSTIBLE
 EXTERIOR FINISHES PROVIDED THE SHEATHING, SIDING, OR
 OTHER EXTERIOR NONCOMBUSTIBLE FINISH EXTENDS A
 HORIZONTAL DISTANCE OF AT LEAST 4 FEET (1220 MM) ON
 BOTH SIDES OF THE FIRE WALL .
 3.FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR
 SHEATHING WHERE THE BUILDING ON EACH SIDE OF THE FIRE
 WALL IS PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR
 903.3.1.2 .
  
 9)2ND NOTICE, IF THE OWNER ELECTS TO COMBINE THE TWO
 LOTS INTO ONE WITH A UNITY OF TITLE THE FIRE WALL WILL
 NOT BE REQUIRED, BUT HIS WOULD BECOME A STIPULATION
 THAT WOULD OCCUR ON THE PROPERTY CONTROL NUMBER, THAT
 THERE COULD NOT BE A LOT SPLIT WITHOUT THE REQUIRED
 FIRE RATINGS FOR A FIRE WALL IN PLACE ALREADY!
  
 10) THE PERMIT APPLICATION DOES NOT INDICATE THIS TO BE
 A SHELL ONLY PLEASE PROVIE THE HANDICAPPED RESTROOM TO
 BE SHOWN ON PLANS OR INDICATE ON THE PERMIT APPLICATION
 THIS ALTERATION AND ADDITION IS TO BE CONSIDERED SHELL
 SPACE ONLY.TSHEET 4 NEW HANDICAPPED RESTROOM, PLEASE
 PROVIDE THE CLEAR FLOOR SPACE FOR FIXTURES ON THE
 PLANS, IT APPEARS THE DOORS MAY SWING INTO THE REQUIRED
 CLEAR FLOOR SPACE. 11-4.22.2 DOORS. ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH 11-4.13.
 DOORS SHALL NOT SWING INTO CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
  
 11) NOT RELAVANT TO THIS REVIEW.
  
 12-13)COMPLIED.
  
 14) COMPLIED.
  
 15) 2ND REQUEST,1203.2 ATTIC SPACES. ENCLOSED ATTICS
 AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING
 MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. BLOCKING AND BRIDGING SHALL BE
 ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF
 AIR. A MINIMUM OF 1 INCH (25 MM) OF AIRSPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF
 SHEATHING.
  
 16A) 2ND REQUEST,SHEET# 1 & 4 NOTE WORK AT THE FRONT
 BUILDING LWALL LINE. PLEASE PROVIDE WHERE THE PROPERTY
 LINE IS LOCATED? ON SHEET# 4.IT APPEARS THAT THE
 FOOTERAMY EXTEND PAST THE PROPERTY LINE.3202.1.1
 STRUCTURAL SUPPORT.A PART OF A BUILDING ERECTED BELOW
 GRADE THAT IS NECESSARY FOR STRUCTURAL SUPPORT OF THE
 BUILDING OR STRUCTURE SHALL NOT PROJECT BEYOND THE LOT
 LINES, EXCEPT THAT THE FOOTINGS OF STREET WALLS OR
 THEIR SUPPORTS WHICH ARE LOCATED AT LEAST 8 FEET (2438
 MM) BELOW GRADE SHALL NOT PROJECT MORE THAN 12 INCHES
 (305 MM) BEYOND THE STREET LOT LINE.
  
 16B)SHEET# 1 THE DEMOLITION PLAN INDICATE A INSWING
 DOOR AT THE FRONT ENTRY, THE NEW REVISED FRONT ENTRY
 INDICATES A NEW FRONT ENTRY DOOR WITH A EXTERIOR SWING
 THAT SWINGS OVER THE PROPERTY LINE.
 3202.2.
  
  
 17) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS
 OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) FIXED WINDOWS- STOREFRONT GLASS SHEET A-2 INDICATES
 STOREFRONT WINDOWS WHERE AS CASEMENT WINDOW PRODUCT
 APPROVALS WERE SUBMITTED.
 B) GLAZED SWING DOORS-OK
 C) HOLLOW CORE METAL DOORS (PAIR) SUBMITTED IS JELD-WIN
 NO GLAZING SHEET A-3 INDICATES A GLAZED UNIT,
 DISCREPANCY, PLEASE CORRECT.
 D) MULLIONS- OK
 E) TRUSS ANCHOR STRAPS AND CONNECTIONS- NOT SUBMITTED
 F) NOT REQUIRED
 G) PRE-ENGINEEREDA/C STANDS- NO A/C WORK IS SHOWN TO
 BE PART OF THIS PERMIT WILL REQUIRE SEPERATE PERMITS/
 REVIEW
 H) ROOFING ASSEMBLIES FL 618-R1 MIAMI-DADE NOA
 03-0501.05 SUBSYSTEMS ARE NOT HIGHLIGHTED, PLEASE
 HIGHLIGHT SUB-SYSTEM TO BE INSTALLED,LOW PRESSURES
 FOR ALL SUB-SYSTEMS WILL REQUIRE ENHANCED FASTENING IN
 ZONES 2 & 3WILL REQUIRE RAS 117 CALCULATIONS. TABLE
 1609.2.1.(2) .
  
 18) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WW.FLORIDABUILDING.ORG
  
 19) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 20) THE MIAMI-DADE PRODUCT APPROVAL REPORTS THAT WERE
 TESTED BEFORE 2004 FBC WILL NEED TO BE REVIEWED BY AN
 ENGINEER TO SEE IF REDUCTIONS NEED TO BE TAKEN. 2004
 FBC 1605.3.1.1 DO NOT ALLOW FOR THE 1/3RD INCREASES
 THAT HAD BEEN TAKEN WHEN THE PRODUCTS WERE TESTED .THE
 PRODUCTS MAY REQUIRE ADDITIONAL FASTENERS. SEE
 CALCULATIONS LISTED UNDER SUB HEADING# 3 ON THE PRODUCT
 APPROVALS, IF THE 2004 CODE IS NOT REFERENCED AN
 ENGINEER WILL NEED TO VERIFY LOADING OF FASTENERS!!!!
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
  
 21-22) WAS FOR SSTORM SHUTTERS ONLY, NOT TO BE USED.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 23)THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH
 THE FOLLOW ITEMS:
 _XXX__ CONTRACTOR / ENGINEER DID NOT INDICATE THE ROOF
 PITCH.
  
 _XXX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XXX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR
 ZONE _2&3__ .
  
  
 _XXX__ NOT KNOWN- THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENERRESISTANCE BE
 LESS THAN THATREQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISEDFASTENER SPACING,
 PREPARED , SIGNEDAND SEALED BY A FLORIDA
 REGISTEREDPROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 __XXX_ NOT KNOWN- THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
  
 24-27 COMPLIED.
  
 28)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 29) NEW COMMENT, SHEET SHEET# 4 INDICATES THE USE OF
 METAL STUDS FOR THE EXTENSION OF THE FRONT ENTRY
 PARAPET. NOTE THE USE OF 22 GAUGE METAL STUDS IS FOR
 NONBEARING INTERIOR USE FOR DRYWALL ONLY. 20 GAUGE
 STRUCTURAL AND OR 18 GAUGE STEEL STUDS AND TRACK WILL
 BE REQUIRED,TABLE 2508.1 ASTM C 1007 L.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]