2008-06-04 12:29:11 | 435 NORTHWOOD RD, LOT 28 07050947 |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07050947 |
| ADD: 435 NORTHWOOD RD |
| CONT: KDN CONSTRUCTION SERVICES, LLC |
| TEL: (561)662-1002 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1) COMPLIED. |
| |
| 2) FL. S. S. 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE FL |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) COMPLIED. |
| |
| 4-6) COMPLIED. |
| |
| 7) 2ND REQUEST, SHEET 4 INDICATES TWO SEPARATE UNITS |
| LOT 28 & 29, WITH A COMMON WALL. THIS IS A SHARED |
| BEARING WALL OR FIRE WALL BETWEEN TWO LOTS OR |
| PROPERTIES REQUIRING RATINGS OF WALL AND ROOF DECKING . |
| 705.1 WHERE A FIRE WALL ALSO SEPARATES GROUPS THAT ARE |
| REQUIRED TO BE SEPARATED BY A FIRE BARRIER WALL, THE |
| MOST RESTRICTIVE REQUIREMENTS OF EACH SEPARATION SHALL |
| APPLY. FIRE WALLS LOCATED ON LOT LINES SHALL ALSO |
| COMPLY WITH SECTION 503.2 . SUCH FIRE WALLS (PARTY |
| WALLS) SHALL PROVIDE A 4-HOUR FIRE-RESISTANCE RATING |
| AND SHALL BE CONSTRUCTED WITHOUT OPENINGS. |
| |
| 8) 2ND REQUEST, FIRE WALLS OR PARTY WALLS, |
| REQUIREMENTS: 705.5 HORIZONTAL CONTINUITY. |
| FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO |
| EXTERIOR WALL AND SHALL EXTEND AT LEAST 18 INCHES (457 |
| MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS. |
| EXCEPTIONS: |
| 1. FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT THE |
| INTERIOR SURFACE OF COMBUSTIBLE EXTERIOR SHEATHING OR |
| SIDING PROVIDED THE EXTERIOR WALL HAS A FIRE-RESISTANCE |
| RATING OF AT LEAST 1 HOUR FOR A HORIZONTAL DISTANCE OF |
| AT LEAST 4 FEET (1220 MM) ON BOTH SIDES OF THE FIRE |
| WALL . OPENINGS WITHIN SUCH EXTERIOR WALLS SHALL BE |
| PROTECTED BY FIRE ASSEMBLIES HAVING A FIRE PROTECTION |
| RATING OF NOT LESS THAN ? HOUR. |
| 2. FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT THE |
| INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR SHEATHING, |
| EXTERIOR SIDING OR OTHER NONCOMBUSTIBLE EXTERIOR |
| FINISHES PROVIDED THE SHEATHING, SIDING, OR OTHER |
| EXTERIOR NONCOMBUSTIBLE FINISH EXTENDS A HORIZONTAL |
| DISTANCE OF AT LEAST 4 FEET (1220 MM) ON BOTH SIDES OF |
| THE FIRE WALL . |
| 3. FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT THE |
| INTERIOR SURFACE OF NONCOMBUSTIBLE EXTERIOR SHEATHING |
| WHERE THE BUILDING ON EACH SIDE OF THE FIRE WALL IS |
| PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 . |
| |
| 9) 2ND NOTICE, IF THE OWNER ELECTS TO COMBINE THE TWO |
| LOTS INTO ONE WITH A UNITY OF TITLE THE FIRE WALL WILL |
| NOT BE REQUIRED, BUT HIS WOULD BECOME A STIPULATION |
| THAT WOULD OCCUR ON THE PROPERTY CONTROL NUMBER, THAT |
| THERE COULD NOT BE A LOT SPLIT WITHOUT THE REQUIRED |
| FIRE RATINGS FOR A FIRE WALL IN PLACE ALREADY! |
| |
| 10) THE PERMIT APPLICATION DOES NOT INDICATE THIS TO BE |
| A SHELL ONLY PLEASE PROVIE THE HANDICAPPED RESTROOM TO |
| BE SHOWN ON PLANS OR INDICATE ON THE PERMIT APPLICATION |
| THIS ALTERATION AND ADDITION IS TO BE CONSIDERED SHELL |
| SPACE ONLY. TSHEET 4 NEW HANDICAPPED RESTROOM, PLEASE |
| PROVIDE THE CLEAR FLOOR SPACE FOR FIXTURES ON THE |
| PLANS, IT APPEARS THE DOORS MAY SWING INTO THE REQUIRED |
| CLEAR FLOOR SPACE. 11-4.22.2 DOORS. ALL DOORS TO |
| ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH 11-4.13. |
| DOORS SHALL NOT SWING INTO CLEAR FLOOR SPACE REQUIRED |
| FOR ANY FIXTURE. |
| |
| 11) NOT RELAVANT TO THIS REVIEW. |
| |
| 12-13) COMPLIED. |
| |
| 14) COMPLIED. |
| |
| 15) 2ND REQUEST, 1203.2 ATTIC SPACES. ENCLOSED ATTICS |
| AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE |
| APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING |
| MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| ENTRANCE OF RAIN. BLOCKING AND BRIDGING SHALL BE |
| ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF |
| AIR. A MINIMUM OF 1 INCH (25 MM) OF AIRSPACE SHALL BE |
| PROVIDED BETWEEN THE INSULATION AND THE ROOF |
| SHEATHING. |
| |
| 16A) 2ND REQUEST, SHEET# 1 & 4 NOTE WORK AT THE FRONT |
| BUILDING LWALL LINE. PLEASE PROVIDE WHERE THE PROPERTY |
| LINE IS LOCATED? ON SHEET# 4. IT APPEARS THAT THE |
| FOOTER AMY EXTEND PAST THE PROPERTY LINE. 3202.1.1 |
| STRUCTURAL SUPPORT.A PART OF A BUILDING ERECTED BELOW |
| GRADE THAT IS NECESSARY FOR STRUCTURAL SUPPORT OF THE |
| BUILDING OR STRUCTURE SHALL NOT PROJECT BEYOND THE LOT |
| LINES, EXCEPT THAT THE FOOTINGS OF STREET WALLS OR |
| THEIR SUPPORTS WHICH ARE LOCATED AT LEAST 8 FEET (2438 |
| MM) BELOW GRADE SHALL NOT PROJECT MORE THAN 12 INCHES |
| (305 MM) BEYOND THE STREET LOT LINE. |
| |
| 16B) SHEET# 1 THE DEMOLITION PLAN INDICATE A INSWING |
| DOOR AT THE FRONT ENTRY, THE NEW REVISED FRONT ENTRY |
| INDICATES A NEW FRONT ENTRY DOOR WITH A EXTERIOR SWING |
| THAT SWINGS OVER THE PROPERTY LINE. |
| 3202.2. |
| |
| |
| 17) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE |
| DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2. GLAZED OPENINGS LOCATED MORE THAN |
| 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS |
| OF THE SMALL MISSILE TEST. |
| |
| FL BLD CODE 1609.1.4: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS |
| ARE AS FOLLOWS: |
| A) FIXED WINDOWS- STOREFRONT GLASS SHEET A-2 INDICATES |
| STOREFRONT WINDOWS WHERE AS CASEMENT WINDOW PRODUCT |
| APPROVALS WERE SUBMITTED. |
| B) GLAZED SWING DOORS-OK |
| C) HOLLOW CORE METAL DOORS (PAIR) SUBMITTED IS JELD-WIN |
| NO GLAZING SHEET A-3 INDICATES A GLAZED UNIT, |
| DISCREPANCY, PLEASE CORRECT. |
| D) MULLIONS- OK |
| E) TRUSS ANCHOR STRAPS AND CONNECTIONS- NOT SUBMITTED |
| F) NOT REQUIRED |
| G) PRE-ENGINEERED A/C STANDS- NO A/C WORK IS SHOWN TO |
| BE PART OF THIS PERMIT WILL REQUIRE SEPERATE PERMITS/ |
| REVIEW |
| H) ROOFING ASSEMBLIES FL 618-R1 MIAMI-DADE NOA |
| 03-0501.05 SUBSYSTEMS ARE NOT HIGHLIGHTED, PLEASE |
| HIGHLIGHT SUB-SYSTEM TO BE INSTALLED, LOW PRESSURES FOR |
| ALL SUB-SYSTEMS WILL REQUIRE ENHANCED FASTENING IN |
| ZONES 2 & 3 WILL REQUIRE RAS 117 CALCULATIONS. TABLE |
| 1609.2.1.(2) . |
| |
| 18) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WW.FLORIDABUILDING.ORG |
| |
| 19) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 20) THE MIAMI-DADE PRODUCT APPROVAL REPORTS THAT WERE |
| TESTED BEFORE 2004 FBC WILL NEED TO BE REVIEWED BY AN |
| ENGINEER TO SEE IF REDUCTIONS NEED TO BE TAKEN. 2004 |
| FBC 1605.3.1.1 DO NOT ALLOW FOR THE 1/3RD INCREASES |
| THAT HAD BEEN TAKEN WHEN THE PRODUCTS WERE TESTED .THE |
| PRODUCTS MAY REQUIRE ADDITIONAL FASTENERS. SEE |
| CALCULATIONS LISTED UNDER SUB HEADING# 3 ON THE PRODUCT |
| APPROVALS, IF THE 2004 CODE IS NOT REFERENCED AN |
| ENGINEER WILL NEED TO VERIFY LOADING OF FASTENERS!!!! |
| 1605.3.1.1 LOAD REDUCTION. |
| 1. IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT OF |
| TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE EFFECT |
| OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN SHALL |
| NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD LOAD AND |
| ANY OF THE VARIABLE LOADS. |
| 2. INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE |
| MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED |
| STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD |
| COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD |
| INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER |
| 23 . |
| |
| 21-22) WAS FOR SSTORM SHUTTERS ONLY, NOT TO BE USED. |
| |
| PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| |
| 23)THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE |
| FOLLOW ITEMS: |
| _XXX__ CONTRACTOR / ENGINEER DID NOT INDICATE THE ROOF |
| PITCH. |
| |
| _XXX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| USED. |
| |
| _XXX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| _2&3__ . |
| |
| |
| _XXX__ NOT KNOWN- THE SYSTEM PROVIDED STATES |
| LIMITATION# 7, SHOULD THE FASTENER RESISTANCE BE LESS |
| THAN THAT REQUIRED, AS DETERMINED BY THE BUILDING |
| OFFICIAL, A REVISED FASTENER SPACING, PREPARED , SIGNED |
| AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF |
| CONSULTANT MAY BE SUBMITTED. |
| |
| __XXX_ NOT KNOWN- THE SYSTEM PROVIDED INDICATES |
| LIMITATION# 9, NO ENHANCED |
| FASTENING ALLOWED. |
| |
| 23) SHEET 8 HAS PENCIL DRAWN BRACING DRAWN IN ON THE |
| PARAPET: 61G15.15-23.002 ENGINEERS MAKING CHANGES IN |
| PLANS SHALL SIGN AND DATE CHANGES, NOT IN PENCIL!!!! |
| |
| 24-27 COMPLIED. |
| |
| 28) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 29) NEW COMMENT, SHEET SHEET# 4 INDICATES THE USE OF |
| METAL STUDS FOR THE EXTENSION OF THE FRONT ENTRY |
| PARAPET. NOTE THE USE OF 22 GAUGE METAL STUDS IS FOR |
| NONBEARING INTERIOR USE FOR DRYWALL ONLY. 20 GAUGE |
| STRUCTURAL AND OR 18 GAUGE STEEL STUDS AND TRACK WILL |
| BE REQUIRED, TABLE 2508.1 ASTM C 1007 L. |
| |
| BUILDING PLAN REVIEW II |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |