2007-07-12 08:46:21 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN TWO OR |
| MORE SETS WITH EACH APPLICATION FOR PERMIT. NO PLANS |
| WERE SUBMITTED FOR THIS ADDRESS. SECTION 106.1.1 |
| |
| 2. THE MINIMUM INFORMATION REQUIRE ON A SET OF PLANS |
| FOLLOWS: |
| A. CODE REFERENCE (FBC-2004 PLUMBING W/2006 |
| AMENDMENTS ETC.). |
| B. OCCUPANCY (INDICATE IF CHANGE OF OCCUPANCY) |
| C. REQUIRED FIXTURES PER TABLE 403.1. |
| D. SANITARY, WATER, STORM, GAS RISER DIAGRAMS AS |
| APPROPRIATE PER SECTION 106.3.5.1.3 |
| E. WATER DISTRIBUTION SYSTEM SIZING CRITERIA & |
| CALCULATIONS |
| F. SITE PLAN SHOWING ROUTING OF SANTIARY, STORM & |
| WATER SERVICE |
| G. COMPLETE DIMENSIONS FOR BATHROOMS, LOCATION OF |
| FIXTURES AND WALL & FLOOR SURFACE MATERIALS |
| H. BACKFLOW PREVENTOR LOCATION |
| I. DRAINAGE SYSTEM PIPING PLAN SHOWING THE LAYOUT OF |
| ALL PIPING & ASSOCIATED CLEANOUTS |
| J. COMPLETE DETAILS OF THE WATER HEATER SHOWING |
| PRESSURE RELIEF VALVE DISCHARGE & THERMAL EXPANSION |
| CONTROL |
| K. COMPLETE DETAILS OF THE METHOD OF DRAINING STORM |
| WATER FROM THE ROOF INCLUDING CALCULATIONS TO VERIFY |
| DRAIN, PIPE, SCUPPER, GUTTER AND/OR DOWNSPOUT SIZE FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. SECTION |
| 106.3.5.1.3. |
| |
| 3. MORE COMMENTS MAY BE FORTHCOMING AFTER THE PLANS ARE |
| SUBMITTED FOR REVIEW. |
| |