Plan Review Notes
Plan Review Notes For Permit 07050947
Permit Number 07050947
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-12 08:46:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR PERMIT. NO PLANS
 WERE SUBMITTED FOR THIS ADDRESS. SECTION 106.1.1
  
 2. THE MINIMUM INFORMATION REQUIRE ON A SET OF PLANS
 FOLLOWS:
 A. CODE REFERENCE (FBC-2004 PLUMBING W/2006
 AMENDMENTS ETC.).
 B. OCCUPANCY (INDICATE IF CHANGE OF OCCUPANCY)
 C. REQUIRED FIXTURES PER TABLE 403.1.
 D. SANITARY, WATER, STORM, GAS RISER DIAGRAMS AS
 APPROPRIATE PER SECTION 106.3.5.1.3
 E. WATER DISTRIBUTION SYSTEM SIZING CRITERIA &
 CALCULATIONS
 F. SITE PLAN SHOWING ROUTING OF SANTIARY, STORM &
 WATER SERVICE
 G. COMPLETE DIMENSIONS FOR BATHROOMS, LOCATION OF
 FIXTURES AND WALL & FLOOR SURFACE MATERIALS
 H. BACKFLOW PREVENTOR LOCATION
 I. DRAINAGE SYSTEM PIPING PLAN SHOWING THE LAYOUT OF
 ALL PIPING & ASSOCIATED CLEANOUTS
 J. COMPLETE DETAILS OF THE WATER HEATER SHOWING
 PRESSURE RELIEF VALVE DISCHARGE & THERMAL EXPANSION
 CONTROL
 K. COMPLETE DETAILS OF THE METHOD OF DRAINING STORM
 WATER FROM THE ROOF INCLUDING CALCULATIONS TO VERIFY
 DRAIN, PIPE, SCUPPER, GUTTER AND/OR DOWNSPOUT SIZE FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SECTION
 106.3.5.1.3.
  
 3. MORE COMMENTS MAY BE FORTHCOMING AFTER THE PLANS ARE
 SUBMITTED FOR REVIEW.
  