Plan Review Notes For Permit 07050923 |
Permit Number |
07050923 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-25 10:49:07 | BUILDING PLAN REVIEW | | PERMIT: 07050923 | | ADD: 700 N CONGRESS AVE | | CONT: ADVANCED ROOFING | | TEL: (954)522-6868 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)THE IMPORTANCE FACTORINDICATED ON THE PROJECT | | DATA CALCULATIONS { 1 }IS IN CORRECT. THE FACTOR FOR | | THE BUILDING IS {1.15}. SEE FBC TABLE 1604.5. THE | | IMPORTANCE FACTOR WILL HAVE AN EFFECT ON THE PRESSURES | | INDICATED IN THE CALCULATIONS. | | | | 2)PROVIDE THE PAGES FROM THE NOA WITH ALL THE | | MATERIALS WHICH CAN BE USED. THIS THE FIRST SIX PAGES | | OF THE NOA. | | | | 3)FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | THE COURT. | | NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|