Plan Review Notes For Permit 07050887 |
Permit Number |
07050887 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-09-17 18:17:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | FROM PREVIOUS LISTS: | | | | 1.)PROVIDE INFORMATION IN REGARDS TO THE EXISTING | | SHUTTERS, SUCH AS A PERMIT NUMBER.IMPACT PROTECTION | | REQUIRED FBC1609.1.4. | | | | 2ND REVIEW - I AM UNABLE TO FIND A HURRICANE SHUTTER | | PERMIT FOR THIS UNIT. | | 3RD REVIEW - CONTRACTOR RESUBMITTED WITH A NOTE STATING | | "HOMEOWNER TOOK IN PROOF OF SHUTTERS 9/14/07".NO | | INFORMATION WAS SUBMITTED UNDER THIS PERMIT NUMBER. | | PLEASE INCORPORATE INTO YOUR PERMIT PACKAGE WHEN YOU | | RESUBMIT. | | | | SEE ALSO FBC EB 507.3. | | | | 2.)STATE HEIGHT OF THE UNIT'S LOCATION.LARGE | | MISSILE IMPACT REQUIRED IN THE FIRST 30' ABOVE GRADE, | | SMALL MISSILE IMPACT REQUIRED ABOVE 30', FBC1609.1.4. | | | | 2ND REVIEW - NON IMPACT RATED PRODUCT APPROVALS WERE | | SUBMITTED.THIS COMMENT IS INFORMATIONAL ONLY; WILL | | NOT NEED TO BE ADDRESSED IF A PERMIT NUMBER FOR THE | | SHUTTERS IS PROVIDED. | | | | | | NEW COMMENT: | | | | 3.)AS APPLICATION DATE IS PRIOR TO JULY 1, 2007 | | REVISIONS, IMPACT PROTECTION IS REQUIRED FOR THIS | | PROJECT.THE HOMEOWNER SHOULD NOT SUBMIT ITEMS | | SEPARATELY AS THAT INFORMATION SHOULD BE A PART OF THE | | PERMIT PACKAGE. | | |
|