Plan Review Notes For Permit 07050882
Permit Number 07050882
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-13 16:43:06DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE PROPOSED RESIDENCE SHEET NO2, PLUMBING RISER
 DIAGRAM: 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 NOTE: THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE REFERENCE THE FOLLOWING
 RED LINE CORRECTIONS ON THIS SHEET FOR THE
 RESUBMITTAL.
 A} WATER CLOSET AND LAV IN THE MASTER BATH.
 B} LAV AND TUB IN THE BATHROOM BETWEEN BEDROOMS
 #1 AND #2.
 C} THE KITCHEN SINK WITH THE DISHWASHER.
 D} THE WASHING MACHINE STACK IS THE WRONG SIZE,
 NEEDS TO BE THREE INCH PER FBC-2004 PLUMBING, SECTION
 406.3.
 E} CLEANOUT REQUIRED FOR THE WASHING MACHINE TO
 BE LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.)
 PER FBC-2004 PLUMBING, SECTION 708.9.
 F} DELETE "SEPTIC" FROM "4" TO SEPTIC SEWER" ON
 THE RESUBMITTAL.
  
 2. PROPOSED GUEST HOUSE SHEET D-1, PLUMBING RISER: PER
 FBC-2004, CHAPTER 1, SECTION 106.1.3, THE SANITARY
 ISOMETRIC RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE REFERENCE THE RED LINE CORRECTIONS ON THIS
 SHEET FOR THE RESUBMITTAL.
 A} LAV AND TUB IN BATHROOM.
 B} KITCHEN SINK.
 C} CLEANOUT FOT THE WASHING MACHINE TO BE LOCATED
 AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER
 FBC-2004 PLUMBING, SECTION 708.9.
 D} PLEASE DELETE "SEPTIC" FROM "4" TO SEPTIC
 SEWER" ON THE RESUBMITTAL.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING. IF AN ARCHITECT OR
 ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY.
 NOTE: THE ENGINEER SEAL APPEARS TO BE INITIALED INSTEAD
 OF BEING SIGNED. ALSO ENGINEER LICENSE NUMBER IS
 MISSING ON SOME SHEETS. PLEASE CORRECT THIS ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721