Plan Review Notes
Plan Review Notes For Permit 07050882
Permit Number 07050882
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-29 18:59:31BUILDING REVIEW CHECKLIST:
 1- NEED TO PROVIDE TWO SETS WITH ORIGINAL ENGINEER'S
 SEAL AND SIGNATURE. ONLYONE SET WAS SIGNED AND
 SEALED.
  
 2- REVISE DRAINAGE PLAN.WATER NEED TO BE DIVERTED
 AWAY FROM THE NEIGHBOR'S PROPERTY.ARROWS SHOWN ON
 SURVEY SHOW WATER LEADING TO THE NEIGHBOR'S PROPERTY.
 REVISE AS REQUIRED.
  
 3- ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED BY
 THE OWNER/AGENT.
 ALSO, COMPLETE INFORMATION ON TOP OF FORM AND REVISE
 OWNER INFORMATION.
  
 4- DRAWINGS TO HAVE CORRECT ADDRESS. THIS PROPERTY IS
 LOCATED ON LOT 8, NOT 9. REVISE AS REQUIRED.
  
 5- OWES $2046.13 FOR UPDATED VALUATION AND RADON FEES
 AND PERMIT FEE BALANCE.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ALLSIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
 ***NOTE: PROVIDE ONLY THE FLROIDA PRODUCT APPROVAL
 COVERPAGE AND SHEET WHERE CONENCTORS IS SHOWN. 7-
 ENGINEER OF RECORDNEEDS TO REVIEW AND APPROVEIN
 WRITING (NOT SIGNING AND SEALING)ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004.
  
 8- REVISE ROOF SHEATHING SPECIFICATIONS. SEE SEC.
 R803.2.3.1 FOR MINIMUM TYPE OF NAIL TO BE USED AND
 SPACING FOR CORNER AREAS.
  
 9- FLOOR PLAN DOESN'T SPECIFY SIZE AND TYPE OF WINDOW
 IN MASTER BEDROOM. NEED INFOMATION TO VERIFY COMPLIANCE
 WITH EGRESS REQUIREMENTS. REVISE ORIGINAL PLAN AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712