2007-10-04 10:02:48NEW RESIDENCE TRUSS DRAWINGS BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND 2004
 FBC.
  
 1- ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 2- "EACH OF THE DRAWINGS IN THE TRUSS DESIGN PACKAGE
 FOR INDIVIDUAL TRUSSES SHALL INCLUDE A TITLE BLOCK
 BEARING THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER
 OF THE TRUSS DESIGN ENGINEER AND THE DATE OF THE
 DRAWINGS" AS REQUIRED BY SEC. 61G15-31.003(5) OF
 FLORIDA ADMINISTRATIVE CODE.
  
 3- ALL GENERAL DETAILS NEED TO HAVE ENGINEER'S ORIGINAL
 SEAL, SIGNATURE AND DATE AS WELL AS ALL ENGINEER'S
 INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 4- SOME OF THE GENERAL DETAILS INCLUDED IN THE TRUSS
 PACKAGE ARE NOT LEGIBLE. PLEASE, MAKE SURE ALL COPIES
 ARE CLEAR AND LEGIBLE PRIOR TO SUBMITTAL. SEC. 106.1.3
 CITY AMENDMENTS TO FBC 2004.
  
 5- UPDATE "TRUSSED VALLEY DETAIL".DETAIL IS REFERRING
 TO ASCE 7-98 AND 100MPH. REVISEAS REQUIRED USING ASCE
 7-02 AND 140MPH.
  
 6- CONNECTORS SPECIFIED FOR ROOF TRUSS G1DON'T RESIST
 THE CALCULATED UPLIFT LOADS. ENGINEER OF RECORD TO
 REVISEROOF FRAMING PLAN AND TRUSS ANCHOR SCHEDULE AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- TRUSS PACKAGE INDEX SHEET IS MISSING THE NAME OF THE
 ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-31.003(5).
  
 8- THESE COMMENTS APPLY TO MAIN RESIDENCE AND GUEST
 HOUSE TRUSS PACKAGE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712