2007-10-04 10:02:48 | NEW RESIDENCE TRUSS DRAWINGS BUILDING REVIEW FIRST |
| CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND 2004 |
| FBC. |
| |
| 1- ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE TRUSS |
| PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| 2- "EACH OF THE DRAWINGS IN THE TRUSS DESIGN PACKAGE |
| FOR INDIVIDUAL TRUSSES SHALL INCLUDE A TITLE BLOCK |
| BEARING THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER |
| OF THE TRUSS DESIGN ENGINEER AND THE DATE OF THE |
| DRAWINGS" AS REQUIRED BY SEC. 61G15-31.003(5) OF |
| FLORIDA ADMINISTRATIVE CODE. |
| |
| 3- ALL GENERAL DETAILS NEED TO HAVE ENGINEER'S ORIGINAL |
| SEAL, SIGNATURE AND DATE AS WELL AS ALL ENGINEER'S |
| INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE |
| AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| |
| 4- SOME OF THE GENERAL DETAILS INCLUDED IN THE TRUSS |
| PACKAGE ARE NOT LEGIBLE. PLEASE, MAKE SURE ALL COPIES |
| ARE CLEAR AND LEGIBLE PRIOR TO SUBMITTAL. SEC. 106.1.3 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 5- UPDATE "TRUSSED VALLEY DETAIL".DETAIL IS REFERRING |
| TO ASCE 7-98 AND 100MPH. REVISEAS REQUIRED USING ASCE |
| 7-02 AND 140MPH. |
| |
| 6- CONNECTORS SPECIFIED FOR ROOF TRUSS G1DON'T RESIST |
| THE CALCULATED UPLIFT LOADS. ENGINEER OF RECORD TO |
| REVISEROOF FRAMING PLAN AND TRUSS ANCHOR SCHEDULE AS |
| REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 7- TRUSS PACKAGE INDEX SHEET IS MISSING THE NAME OF THE |
| ENGINEER OF RECORD AS REQUIRED BY SEC. |
| 61G15-31.003(5). |
| |
| 8- THESE COMMENTS APPLY TO MAIN RESIDENCE AND GUEST |
| HOUSE TRUSS PACKAGE. |
| |