Plan Review Notes
Plan Review Notes For Permit 07050881
Permit Number 07050881
Review Stop M
Sequence Number 1
Notes
Date Text
2007-05-29 10:48:04*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE SHOW THE SEER OF THE A/C SYSTEMS ON THE
 MECHANICAL PLANS.
  
 3) PLEASE SHOW THE LOCATION OF THE CLOTHES DRYER VENTS
 TERMINATION ON THE MECHANICAL PLANS, BE ADVISED THE
 CLOTHES DRYERS MAY NOT DISCHARGE NEAR THE A/C CONDENSER
 UNITS, SEE 2004 FBC/M 501.2 .
  
 4) SEE COOLING LOAD CALCULATIONS PAGE 3 SHOWS NO
 MINIMUM AND MAXIMUM VELOCITY'S, PLEASE CORRECT.
  
 5) SEE MECHANICAL PLANS FOR THE COTTAGE THE 6" MAIN
 SUPPLY DUCT TO THE MIXING BOX AT 800 CFM'S WOULD BE A
 HIGH PRESSURE DUCT, PLEASE SHOW ON PLANS THAT THE DUCTS
 ARE TO BE METAL AS FLEX DUCT IS NOT RATED FOR HIGH
 PRESSURE, OR RE-CALCULATE DUCT CALCULATIONS.
  
 6) SEE MECHANICAL PLANS MAIN HOUSE THE TWO 6" MAIN
 SUPPLY AIR DUSTS TO THE MIXING BOXES APPEARS TO BE A
 MISTAKE PLEASE RE-CALCULATE DUCT CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.