Plan Review Notes
Plan Review Notes For Permit 07050881
Permit Number 07050881
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-30 09:38:56 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE INFORMATION ON THE RISER DIAGRAM INDICATES THE
 METER AND PANEL ARE "EXISTING", THE APPLICATION IS FOR
 A NEW RESIDENCE.
  
 2} THE WATER HEATERS APPEARS TO PLUG IN TO A 220 VOLT
 RECEPTACLE.SEE 422.16 FOR CORD CONNECTED APPLIANCES.
 CHANGE SYMBOL TO A DISCONNECT IF REQUIRED.
  
 3} SEE 210.52(C)(5) FOR RECEPTACLE REQUIREMENTS AT THE
 "PASS THROUGH".NOTE THE EXEPTION.
  
 4} A SMOKE ALARM IS REQUIRED "OUTSIDE--IN THE IMMEDIATE
 VICINITY" OF THE BEDROOM IN THE GUEST HOUSE PER 313.1.1
 FBC RESIDENTIAL.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. ALL SHEETS.
  
 NOTE: THE ABSENCE OF T.V. AND PHONE DEVICES ON THE PLAN
 WILL DICTATE ANOTHER SET OF PLANS BE SUBMITTED SHOWING
 THOSE LOCATIONS AND ANOTHER PERMIT APPLIED FOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718