Plan Review Notes For Permit 07050881 |
Permit Number |
07050881 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-29 18:58:20 | BUILDING REVIEW CHECKLIST: | | 1- NEED TO PROVIDE TWO SETS WITH ORIGINAL ENGINEER'S | | SEAL AND SIGNATURE. ONLYONE SET WAS SIGNED AND | | SEALED. | | | | 2- REVISE DRAINAGE PLAN.WATER NEED TO BE DIVERTED | | AWAY FROM THE NEIGHBOR'S PROPERTY.ARROWS SHOWN ON | | SURVEY SHOW WATER LEADING TO THE NEIGHBOR'S PROPERTY. | | REVISE AS REQUIRED. | | | | 3- ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED BY | | THE OWNER/AGENT. | | ALSO, COMPLETE INFORMATION ON TOP OF FORM AND REVISE | | OWNER INFORMATION. | | | | 4- DRAWINGS TO HAVE CORRECT ADDRESS. THIS PROPERTY IS | | LOCATED ON LOT 8, NOT 9. REVISE AS REQUIRED. | | | | 5- OWES $284.27 FOR UPDATED VALUATION AND RADON FEES. | | | | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | 9B-72 FOR: | | A) ALLSIMPSON STRUCTURAL CONNECTORS SPECIFIED ON | | PLANS. | | ***NOTE: PROVIDE ONLY THE FLROIDA PRODUCT APPROVAL | | COVERPAGE AND SHEET WHERE CONENCTORS IS SHOWN. 7- | | ENGINEER OF RECORDNEEDS TO REVIEW AND APPROVEIN | | WRITING (NOT SIGNING AND SEALING)ALL PRODUCT | | APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS | | TO FBC 2004. | | | | 8- REVISE ROOF SHEATHING SPECIFICATIONS. SEE SEC. | | R803.2.3.1 FOR MINIMUM TYPE OF NAIL TO BE USED AND | | SPACING FOR CORNER AREAS. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|