2008-09-04 15:50:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS.
 *** DENIED ***
  
 1) THE MECHANICAL PLANS ON FILE WERE SIGNED AND SEALED
 BY AN ENGINEER (EDWARD J. KRANZ) SO ONLY HE CAN MAKE
 REVISIONS TO THEM, PER FAC 61G15-23.002.
  
 2) ENERGY CALCULATION ON FILE ARE CALLING FOR HEAT PUMP
 UNIT, REVISED MECHANICAL PLAN IS SHOWING A STRAIGHT
 COOLING SYSTEM. PLEASE CORRECT PLANS OR REVISE ENERGY
 CALCULATIONS, PER 2004 FBC 13-103.3.
  
 3) PLAN M-3 A/C SCHEDULE IS CALLING FOR A 60 AMP FUSE
 FOR A 5 KW HEATER, PLEASE CORRECT TO MANUFACTURES
 SPEC'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]