Plan Review Notes
Plan Review Notes For Permit 07050872
Permit Number 07050872
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-16 07:48:50 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE GENERATOR MUST BE PERMITTED SEPARATELY. THE
 MANUAL TRANSFER SWITCH MAY BE LEFT ON THE RISER WITH
 THIS PERMIT, BUT MANUFACTURERS SPECIFICATIONS MUST BE
 SUBMITTED FOR REVIEW PRIOR TO A PERMIT BEING ISSUED.
 MAKE A NOTE ON THE RISER DIAGRAM, SHEET E-2, THAT THE
 GENERATOR WILL BE PERMITTED SEPARATELY. REMOVE THE "
 +NEW DRIVEWAY+NEW GENERATOR" PENCIL ADDITIONS IN THE
 DESCRIPTION ON THE APPLICATION. IF ADDING TO THE
 DESCRIPTION INCREASE THE VALUE TO INCLUDE SAME.
  
 2}NOTE THE SIZE PER 250.122, #2 IS EXCESSIVE, AND
 ALTHOUGH PERMITTED, WILL PROBABLY RESULT IN A LATER
 REVISION. SEE TABLE. THIS COMMENT REFERS TO THE PANEL
 "A" FEED FROM THE TRANSFER SWITCH.
  
 3} REGARDING NOTE #5, PREVIOUS REVIEW "THERE IS
 EQUIPMENT LISTED IN THE CALCULATIONS THAT ARE NOT ON
 ANY PANEL SCHEDULES. SEE REVIEWED PLAN." THE POOL PANEL
 WITH A 10240 W CALCULATED LOAD STILL IS LISTED IN THE
 LOAD CALCULATION(SERVICE), 6283 VA IN THE POOL
 EQUIPMENT CALCULATION AND ONLY A PUMP AND LIGHT ARE
 LISTED IN PANEL "A". PLEASE CORRELATE TO INDICATE
 ACTUAL CONDITIONS.
  
 4} PANEL "A", CIRCUIT 1,3,SHEET E-2, LISTS #3
 CONDUCTORS FEEDING PANEL "B", AND THE RISER FEEDERS ARE
 LISTED AS #2. PLEASE VERIFY EXISTING CONDITIONS AND
 CORRECT ON PLAN.
  
 5} CIRCUITS 16 AND 18, PANEL "A" ARE REVERSED FROM THE
 NUMBERED CIRCUITS ON SHEET E-2. SMALL APPLIANCE
 (REQUIRED) AND LIGHTING.
  
 NOTE #1: CIRCUIT # A24,FOR THE SMOKE DETECTORS MUST
 BE ON A AFCI PER 210.12, THE OUTSIDE LIGHTS ARE ON THIS
 SAME CIRCUIT, NO VIOLATION, JUST A NOTE.
 #2: ALTHOUGH THE GENERATOR IS NOT BEING
 REVIEWED AT THIS TIME, IT WAS NOTED THAT THE GENERATOR
 CALCULATION IS 101 AMPS (24KW), THE SPEC'S SUBMITTED
 ARE FOR A 20KW GENERATOR WITH AN OUTPUT OF 84 AMPS.
  
 THE DESIGNER OF RECORD IS THE ENGINEER THAT SEALED THE
 PLAN, THE RESPONSE FOR THE PREVIOUS REVIEW WAS SIGNED
 BY THE ARCHITECT. PLEASE SEE THAT ALL GET A COPY OF
 THESE COMMENTS.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
 ANSWER REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  