| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE GENERATOR MUST BE PERMITTED SEPARATELY. THE |
| MANUAL TRANSFER SWITCH MAY BE LEFT ON THE RISER WITH |
| THIS PERMIT, BUT MANUFACTURERS SPECIFICATIONS MUST BE |
| SUBMITTED FOR REVIEW PRIOR TO A PERMIT BEING ISSUED. |
| MAKE A NOTE ON THE RISER DIAGRAM, SHEET E-2, THAT THE |
| GENERATOR WILL BE PERMITTED SEPARATELY. REMOVE THE " |
| +NEW DRIVEWAY+NEW GENERATOR" PENCIL ADDITIONS IN THE |
| DESCRIPTION ON THE APPLICATION. IF ADDING TO THE |
| DESCRIPTION INCREASE THE VALUE TO INCLUDE SAME. |
| |
| 2}NOTE THE SIZE PER 250.122, #2 IS EXCESSIVE, AND |
| ALTHOUGH PERMITTED, WILL PROBABLY RESULT IN A LATER |
| REVISION. SEE TABLE. THIS COMMENT REFERS TO THE PANEL |
| "A" FEED FROM THE TRANSFER SWITCH. |
| |
| 3} REGARDING NOTE #5, PREVIOUS REVIEW "THERE IS |
| EQUIPMENT LISTED IN THE CALCULATIONS THAT ARE NOT ON |
| ANY PANEL SCHEDULES. SEE REVIEWED PLAN." THE POOL PANEL |
| WITH A 10240 W CALCULATED LOAD STILL IS LISTED IN THE |
| LOAD CALCULATION(SERVICE), 6283 VA IN THE POOL |
| EQUIPMENT CALCULATION AND ONLY A PUMP AND LIGHT ARE |
| LISTED IN PANEL "A". PLEASE CORRELATE TO INDICATE |
| ACTUAL CONDITIONS. |
| |
| 4} PANEL "A", CIRCUIT 1,3,SHEET E-2, LISTS #3 |
| CONDUCTORS FEEDING PANEL "B", AND THE RISER FEEDERS ARE |
| LISTED AS #2. PLEASE VERIFY EXISTING CONDITIONS AND |
| CORRECT ON PLAN. |
| |
| 5} CIRCUITS 16 AND 18, PANEL "A" ARE REVERSED FROM THE |
| NUMBERED CIRCUITS ON SHEET E-2. SMALL APPLIANCE |
| (REQUIRED) AND LIGHTING. |
| |
| NOTE #1: CIRCUIT # A24,FOR THE SMOKE DETECTORS MUST |
| BE ON A AFCI PER 210.12, THE OUTSIDE LIGHTS ARE ON THIS |
| SAME CIRCUIT, NO VIOLATION, JUST A NOTE. |
| #2: ALTHOUGH THE GENERATOR IS NOT BEING |
| REVIEWED AT THIS TIME, IT WAS NOTED THAT THE GENERATOR |
| CALCULATION IS 101 AMPS (24KW), THE SPEC'S SUBMITTED |
| ARE FOR A 20KW GENERATOR WITH AN OUTPUT OF 84 AMPS. |
| |
| THE DESIGNER OF RECORD IS THE ENGINEER THAT SEALED THE |
| PLAN, THE RESPONSE FOR THE PREVIOUS REVIEW WAS SIGNED |
| BY THE ARCHITECT. PLEASE SEE THAT ALL GET A COPY OF |
| THESE COMMENTS. |
| |
| PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| SEPARATELY TO EXPEDITE THE REVIEW PROCESS. |
| ANSWER REVIEW COMMENTS IN WRITING. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |