Plan Review Notes For Permit 07050872 |
Permit Number |
07050872 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-14 10:25:28 | DENIED | | REFERENCE: | | ** FBC-2004 FUEL GAS. | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | REQUIREMENTS. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE. | | ** FLORIDA STATUTES. | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1. NOTE: THERE IS NO INDICATION OF A GENERATOR BEING | | APPLIED FOR ON THE PERMIT APPLICATION. ON THE PERMIT | | APPLICATION IT STATES "DESCRIBE PROJECT IN DETAIL | | (FAILURE TO DO SO MAY RESULT IN DELAYS)". A SEPERATE | | PERMIT IS REQUIRED FOR THE GENERATOR. | | A} SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT (GENERATOR) TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | B} A GAS PERMIT CAN NOT BE ISSUED UNTIL | | A GEN/RES PERMIT APPLICATION HAS BEEN | | APPLIED FOR AND APPROVED BY ZONING FOR | | THE GENERATOR LOCATION. | | | | 2. REMOVE GENERATOR AND GAS FROM RESUBMITTED PRINTS. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|