Plan Review Notes
Plan Review Notes For Permit 07050872
Permit Number 07050872
Review Stop G
Sequence Number 1
Notes
Date Text
2007-06-14 10:25:28DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: THERE IS NO INDICATION OF A GENERATOR BEING
 APPLIED FOR ON THE PERMIT APPLICATION. ON THE PERMIT
 APPLICATION IT STATES "DESCRIBE PROJECT IN DETAIL
 (FAILURE TO DO SO MAY RESULT IN DELAYS)". A SEPERATE
 PERMIT IS REQUIRED FOR THE GENERATOR.
 A} SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT (GENERATOR) TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 B} A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 2. REMOVE GENERATOR AND GAS FROM RESUBMITTED PRINTS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721