2007-06-05 12:32:52 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} ALL COMMENTS ARE REQUIREMENTS OF THE 2004 FLORIDA |
| BUILDING CODE AND REFERENCED MATERIAL THEREIN, |
| INCLUDING THE 2005 NEC.. NOTE #4, SHEET E-1 REFERENCES |
| INCORRECT CYCLES. |
| |
| 2} NOTE 14, SHEET E-1DOES NOPT ALLOW FOR NMC. WHILE NOT |
| IN VIOLATION, IF IT REMAINS AS WRITTEN, ALL WIRING MUST |
| BE INSTALLED IN CONDUIT, OR A REVISION WILL BE REQUIRED |
| TO CHANGE THIS NOTE AT A LATER DATE, AND COULD CREATE A |
| WORK HOLD UNTILL SUBMITTED AND REVIEWED. |
| |
| 3} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| FROM THE FIRST MEANS OF DISCONNECT. 250.6. ALSO NOTE |
| THE SIZE PER 250.122, #2 IS EXCESSIVE, AND ALTHOUGH |
| PERMITTED, WILL PROBABLY RESULT IN A LATER REVISION. |
| SEE TABLE. |
| |
| 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE |
| ARTICLE QUOTED, 220.11, IS INCORRECT, PANEL "C" SHOULD |
| NOT BE CALCULATED SEPARATELY. |
| |
| 5} THERE IS EQUIPMENT LISTED IN THE CALCULATIONS THAT |
| ARE NOT ON ANY PANEL SCHEDULES. SEE REVIEWED PLAN. |
| |
| 6} LOCATE THE POOL PANEL ON THE PLAN AND RISER. |
| |
| 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED |
| IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE |
| SAME ON PLANS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |