Plan Review Notes
Plan Review Notes For Permit 07050872
Permit Number 07050872
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-05 12:32:52 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} ALL COMMENTS ARE REQUIREMENTS OF THE 2004 FLORIDA
 BUILDING CODE AND REFERENCED MATERIAL THEREIN,
 INCLUDING THE 2005 NEC.. NOTE #4, SHEET E-1 REFERENCES
 INCORRECT CYCLES.
  
 2} NOTE 14, SHEET E-1DOES NOPT ALLOW FOR NMC. WHILE NOT
 IN VIOLATION, IF IT REMAINS AS WRITTEN, ALL WIRING MUST
 BE INSTALLED IN CONDUIT, OR A REVISION WILL BE REQUIRED
 TO CHANGE THIS NOTE AT A LATER DATE, AND COULD CREATE A
 WORK HOLD UNTILL SUBMITTED AND REVIEWED.
  
 3} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6. ALSO NOTE
 THE SIZE PER 250.122, #2 IS EXCESSIVE, AND ALTHOUGH
 PERMITTED, WILL PROBABLY RESULT IN A LATER REVISION.
 SEE TABLE.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 ARTICLE QUOTED, 220.11, IS INCORRECT, PANEL "C" SHOULD
 NOT BE CALCULATED SEPARATELY.
  
 5} THERE IS EQUIPMENT LISTED IN THE CALCULATIONS THAT
 ARE NOT ON ANY PANEL SCHEDULES. SEE REVIEWED PLAN.
  
 6} LOCATE THE POOL PANEL ON THE PLAN AND RISER.
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE
 SAME ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  