Plan Review Notes
Plan Review Notes For Permit 07050844
Permit Number 07050844
Review Stop M
Sequence Number 2
Notes
Date Text
2007-05-29 15:03:51*** DENIED ***
 1) COOLING LOAD CALCULATIONS SUBMITTED ARE FOR 2265
 SQUARE FEET AND A 4.7 TON A/C SYSTEM. THE ADDITION IS
 ONLY 480 SQUARE FEET. PLEASE SUBMIT CORRECT COOLING
 LOAD CALCULATIONS, SEE 2004 FBC 13-607.1.ABC.1.
  
 2) PLEASE SUBMIT TWO COPIES OF ALL PAPER WORK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.