Plan Review Notes For Permit 07050844 |
Permit Number |
07050844 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-23 10:09:44 | *** DENIED *** | | 1) THE MECHANICAL PERMIT MAY NOT ATTACHE TO THE MASTER | | PERMIT AS THE MASTER PERMIT SHOWED NO MECHANICAL WORK | | TO BE DONE. | | | | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | 3) THE JOB ADDRESS MUST APPEAR ON ALL PLANS, SEE 2004 | | FBC CITY WPB AMEND. 106.1.3. | | | | 4) PLEASE SUBMIT ENERGY CALCULATIONS,PER 2004 FBC | | 13-101.2.2, (12-8-06 REVISION). | | | | 5) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 | | FBC 13-607.1.ABC.1. | | | | 6) IT APPEARS THE AIR HANDLER IS LOCATED IN THE | | BATHROOM AND THE RETURN AIR DUCT IS AN OPEN DUCT, | | RETURN AIR MAY NOT COME FROM THE BATHROOM THIS WILL | | HAVE TO BE A CLOSED DUCT SYSTEM, PLEASE CORRECT, SEE | | 2004 FBC/R M1602.2(4). | | | | 7) PLEASE SHOW THE TOTAL AND SENSIBLE COOLING BTU'S ON | | THE PLANS. | | | | 8) PLEASE BE ADVISED YOU WILL NEED TO FILE A NOTICE OF | | COMMENCEMENT FOR THE A/C WORK. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|