Plan Review Notes
Plan Review Notes For Permit 07050833
Permit Number 07050833
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-11 16:33:14DENIED
 REFERENCE:
 ** FBC-2004 SECTIONS424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: PLEASE CORRELATE THE EQUIPMENT LAYOUT WITH THE
 LEGEND. THE EQUIPMENT IDENTIFIED WITH THE LETTERS ON
 THE EQUIPMENT LAYOUT DOES NOTMATCH THE EQUIPMENT
 IDENTIFIED BY LETTERS IN THE LEGEND. PLEASE CORRECT ON
 THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721