 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THERE IS
 ONLY ONE SMALL APPLIANCE CIRCUIT LISTED ON THE PANEL
 SCHEDULE.
  
 2} THERE IS A RECEPTACLE SHOWM AT THE WATER HEATER. A
 DISCONNECT IS REQUIRED PER 422.16(A).
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE.SEE HEAT DETECTOR FOR
 KITCHEN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  