Plan Review Notes
Plan Review Notes For Permit 07050823
Permit Number 07050823
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-13 17:42:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)YOU HAVE STATED ON THE INSTALLATION SCHEDULE THAT
 YOU ARE DESIGNING TO -77PSF, BUT HAVE CIRCLED -62 ON
 THE PRODUCT APPROVAL.C2 CONNECTION WITH A -77 DESIGN
 PRESSURE REQUIRES 5"SPACING, SEE OPENING 4.PLEASE
 REVISE EITHER THE DESIGN PRESSURES ON THE INSTALLATION
 SCHEDULE OR ANCHOR SPACING.CHECK ALL OPEININGS.
  