2007-06-21 07:42:20 | *** UNSAT2ND REVIEW *** |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW NEED |
| TO BE ADDRESSED ALONG WITH NEW COMMENTS BASED ON |
| INFORMATION AND/OR CHANGES NOW ON PLANS. |
| |
| 1) NOTE:PLEASE SEE NOT ALL CODES AS LISTED ARE SHOWN |
| ON PLANS. PLEASE SEE THE YEAR OF THE CODE DOES NEED TO |
| BE STATED. ONLY THE FBC WAS ADDED WITH THE CORRECT YEAR |
| AND AMENDMENTS. |
| ** PREVIOUS NOTE** |
| PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO |
| BE STATED ON PLANS. |
| PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| PLEASE LIST THE FOLLOWING |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE:PLEASE DO NOT REFERENCE LICENSURE UNDER FS |
| 481.229 AS THIS SECTION OF THE FS IS FOR ARCHITECTS AND |
| EXEMPTIONS. THE STATUTE IN WHICH THE CONTRACTOR MAY |
| SIGN FOR THIS SCOPE OF WORK DOES NOT NEED TO BE ON |
| PLANS. |
| |
| 3) NOTE: PLEASE SEE THE PREVIOUS NOTE MENTIONED THAT |
| EITHER SMOKE ALARMS OR SMOKE DETECTORS WOULD NEED TO BE |
| BROUGHT UP TO CODE AND WOULD NEED TO BE SHOWN DEPENDING |
| ON THE SYSTEM BEING INSTALLED. PLEASE SEE THE PLANS AND |
| NOTES INDICATE THESE AS SD FOR SMOKE DETECTORS, YET THE |
| NOTES MENTIONS THESE AS 120V WITH BATTERY BACK UP? |
| PLEASE KNOW SMOKE ALARMS ARE DEVICE WHICH NOT ONLY |
| DETECT BUT ALSO SOUND AN ALARM. IF INSTALLING SMOKE |
| ALARMS AS SHOWN, THESE DEVICES ONLY DETECT AND SIGNAL |
| FOR ALARM. NO SOUNDING, HORN DEVICES WERE LOCATED ON |
| PLANS. PLEASE BE SURE THE SYSTEM IN WHICH IS BEING |
| PROPOSED IS COMPLETE. IF THESE ARE 120V W/ BATTERY BACK |
| UP WHICH DETECT AND SOUND, PLEASE CHANGE TO SA AND |
| SMOKE ALARM DESIGNATION? PLEASE ALSO SEE 210.12 FOR |
| REQUIRED ARC FAULT AS CIRCUITING AS NEEDED IS NOT ON |
| PLANS OR THE BRIEF PANEL SCHEDULE SUBMITTED. NFPA-72 |
| 11.5.1.1, 11.8.3. |
| |
| 4) NOTE: PLEASE SEE THE PANEL SCHEDULE AS SUBMITTED IS |
| ONLY INDICATING NEW CIRCUITS HOWEVER THESE IS MISSING |
| CONDUCTOR SIZE FOR OVEN AND NO BREAKER SIZE OR WIRE |
| SIZE IS BEING SHOWN FOR THE NEW COOK-TOP? |
| PLEASE SUBMIT THE COMPLETED PANEL SCHEDULE FOR NEW AND |
| EXISTING CIRCUITS IN THESE AREAS BEING RENOVATED. |
| 408.4, 240.4, 310.16 |
| |
| 5) NOTE:PLEASE SEE THAT NO HAND WRITTEN ITEMS ARE |
| PERMITTED ON PLANS IN PEN OR PENCIL. PLEASE SEE LIGHTS |
| OVER KITCHEN COUNTER WHICH WERE ADDED IN PEN. |
| FBC ADMIN SECT 106.1, 106.3.5.1.2 |
| |
| 6) NOTE: PLEASE SEE 210.70A1AS THE SWITCHES FOR BATH |
| ROOM LIGHTING SHOULD BE IN THE BATHROOM. |
| (1) HABITABLE ROOMS AT LEAST ONE WALL SWITCH-CONTROLLED |
| LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE |
| ROOM AND BATHROOM. |
| |
| ** PLEASE KNOW THE RESPONSES TO COMMENTS NEED NOT BE ON |
| PLANS ONLY THE NEEDED DETAIL FOR CONSTRUCTION OR CODE |
| COMPLIANCE. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |