Plan Review Notes
Plan Review Notes For Permit 07050744
Permit Number 07050744
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-21 07:42:20*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW NEED
 TO BE ADDRESSED ALONG WITH NEW COMMENTS BASED ON
 INFORMATION AND/OR CHANGES NOW ON PLANS.
  
 1) NOTE:PLEASE SEE NOT ALL CODES AS LISTED ARE SHOWN
 ON PLANS. PLEASE SEE THE YEAR OF THE CODE DOES NEED TO
 BE STATED. ONLY THE FBC WAS ADDED WITH THE CORRECT YEAR
 AND AMENDMENTS.
 ** PREVIOUS NOTE**
 PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO
 BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE:PLEASE DO NOT REFERENCE LICENSURE UNDER FS
 481.229 AS THIS SECTION OF THE FS IS FOR ARCHITECTS AND
 EXEMPTIONS. THE STATUTE IN WHICH THE CONTRACTOR MAY
 SIGN FOR THIS SCOPE OF WORK DOES NOT NEED TO BE ON
 PLANS.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTE MENTIONED THAT
 EITHER SMOKE ALARMS OR SMOKE DETECTORS WOULD NEED TO BE
 BROUGHT UP TO CODE AND WOULD NEED TO BE SHOWN DEPENDING
 ON THE SYSTEM BEING INSTALLED. PLEASE SEE THE PLANS AND
 NOTES INDICATE THESE AS SD FOR SMOKE DETECTORS, YET THE
 NOTES MENTIONS THESE AS 120V WITH BATTERY BACK UP?
 PLEASE KNOW SMOKE ALARMS ARE DEVICE WHICH NOT ONLY
 DETECT BUT ALSO SOUND AN ALARM. IF INSTALLING SMOKE
 ALARMS AS SHOWN, THESE DEVICES ONLY DETECT AND SIGNAL
 FOR ALARM. NO SOUNDING, HORN DEVICES WERE LOCATED ON
 PLANS. PLEASE BE SURE THE SYSTEM IN WHICH IS BEING
 PROPOSED IS COMPLETE. IF THESE ARE 120V W/ BATTERY BACK
 UP WHICH DETECT AND SOUND, PLEASE CHANGE TO SA AND
 SMOKE ALARM DESIGNATION? PLEASE ALSO SEE 210.12 FOR
 REQUIRED ARC FAULT AS CIRCUITING AS NEEDED IS NOT ON
 PLANS OR THE BRIEF PANEL SCHEDULE SUBMITTED. NFPA-72
 11.5.1.1, 11.8.3.
  
 4) NOTE: PLEASE SEE THE PANEL SCHEDULE AS SUBMITTED IS
 ONLY INDICATING NEW CIRCUITS HOWEVER THESE IS MISSING
 CONDUCTOR SIZE FOR OVEN AND NO BREAKER SIZE OR WIRE
 SIZE IS BEING SHOWN FOR THE NEW COOK-TOP?
 PLEASE SUBMIT THE COMPLETED PANEL SCHEDULE FOR NEW AND
 EXISTING CIRCUITS IN THESE AREAS BEING RENOVATED.
 408.4, 240.4, 310.16
  
 5) NOTE:PLEASE SEE THAT NO HAND WRITTEN ITEMS ARE
 PERMITTED ON PLANS IN PEN OR PENCIL. PLEASE SEE LIGHTS
 OVER KITCHEN COUNTER WHICH WERE ADDED IN PEN.
 FBC ADMIN SECT 106.1, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE 210.70A1AS THE SWITCHES FOR BATH
 ROOM LIGHTING SHOULD BE IN THE BATHROOM.
 (1) HABITABLE ROOMS AT LEAST ONE WALL SWITCH-CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE
 ROOM AND BATHROOM.
  
 ** PLEASE KNOW THE RESPONSES TO COMMENTS NEED NOT BE ON
 PLANS ONLY THE NEEDED DETAIL FOR CONSTRUCTION OR CODE
 COMPLIANCE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]