Plan Review Notes
Plan Review Notes For Permit 07050728
Permit Number 07050728
Review Stop P
Sequence Number 2
Notes
Date Text
2007-10-02 13:06:38DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 **PLEASE NOTE THAT THE RESUBMITTED PLANS NEED THE
 FOLLOWING CORRECTIONS TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 W/05 & 06 REV. SECTION 1003.5.3 THE
 INLET PIPING SHALL EXTEND TO 24 INCHES BELOW THE WATER
 LEVEL. THE OUTLET PIPE SHALL START 8 INCHES ABOVE THE
 BOTTOM OF THE INTERCEPTOR.
  
 2. PER THE APPROVED PLANNING, ZONING AND BUILDING
 DEPARTMENT, STANDARD GREASE TRAP DETAIL, THE MANHOLE
 WITH LID SHALL BE A MINIMUM OF 24 INCHES AND THE LID
 SHALL BE DESIGNATED "GREASE" ON IT. PLEASE REFERENCE
 THE ATTACHED APPROVED CITY OF WEST PALM BEACH, STANDARD
 GREASE TRAP DETAIL FOR FUTURE SUBMITTALS.
  
 3. PER FBC-2004 W/05 & 06 REV. SECTION 708.3.3
 CLEANOUTS SHALL BE INSTALLED AT EACH CHANGE OF
 DIRECTION OF THE BUILDING DRAIN OR HORIZONTAL WASTE OR
 SOIL LINES GREATER THAN 45 DEGREES.
  
 4. THE RESUBMITTED PLANS TITLE BLOCK INFORMATION IS
 INCOMPLETE FOR RIZA N. ALTAN P. E. AND TORQUOISE
 CONSULTING INC., PER FAC-61G15-23.002 SEAL SIGNATURE
 AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
  
 5. NOTE: THE NOTICE OF COMMENCEMENT HAS EXPIRED PER FS
 713.13(2) IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND NO
 FURTHER EFFECT. A NEW NOTICE OF COMMENCEMENT IS
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 END OF COMMENTS:
  