Date |
Text |
2007-06-13 08:19:52 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. VALUE IS TO LOW FOR THIS PROJECT, PLEASE PROVIDE |
| COPY OF THE CONTRACT TO VERIFY THE VALUE. |
| PER FBC-2004, CHAPTER 1, SECTION |
| 108.3, BUILDING PERMIT VALUATION: IF IN |
| THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF THE BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED. FOR |
| PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, NORMAL SITE WORK (EXCAVATION AND |
| BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| VALUE. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS ECT.) WITH |
| REGIONAL ADJUSTMENTS FOR LOCATION AS |
| PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 |
| PLUMBING (9): PLEASE PROVIDE A SANITARY ISOMETRIC |
| DRAWING OF GREASE INTERCEPTOR PIPING WITH PIPE SIZES, |
| CLEANOUT LOCATIONS, AND GREASE INTERCEPTOR SIZES AND |
| LOCATION. |
| NOTE: GREASE INTERCEPTOR LOCATION NEEDS APPROVAL FROM |
| ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT. |
| PLEASE REFERENCE COMMENT NUMBER THREE (3) FOR |
| ENVIRONMENTAL COMPLIANCE INFORMATION. |
| |
| 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 |
| PLUMBING (12) ENVIRONMENTAL REQUIREMENTS: THE GREASE |
| INTERCEPTORS SHALL BE SIZED AND LOCATED BY |
| ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT. |
| PLEASE CONTACT RODNEY COMPO, (561) 822-2272 OR CALVIN |
| WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561) |
| 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected] |
| AND [email protected]. MUNICIPAL CODE ARTICLE III |
| SECTION 90-124. |
| NOTE: WRITTEN CONFORMATION FROM ENVIRONMENTAL |
| COMPLIANCE IS REQUIRED BEFORE PERMIT CAN BE ISSUED. |
| |
| 4. PLEASE INDICATE HOW THE RATE OF FLOW IS TO BE |
| CONTROLLED PER FBC-2004 PLUMBING, SECTION 1003.3.4.2: |
| GREASE TRAPS SHALL BE EQUIPPED WITH DEVICES TO CONTROL |
| THE RATE OF WATER FLOW SO THAT THE WATER FLOW DOES NOT |
| EXCEED THE RATED FLOW. THE FLOW-CONTROL DEVICE SHALL BE |
| VENTED AND TERMINATE NOT LESS THAN 6 INCHES (152MM) |
| ABOVE THE FLOOD RIM LEVEL OR BE INSTALLED IN ACCORDANCE |
| WITH THE MANUFACTURER'S INSTRUCTIONS. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |