Plan Review Notes For Permit 07050714 |
Permit Number |
07050714 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-07-11 15:49:06 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY | | OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FROM PREVIOUS LIST: | | | | 2.)OPENINGS 8 THROUGH 17, INSTALLATION SCHEDULE | | SPECIFIES CBS, A FOR BOTTOM MOUNTING TYPE."A" IS | | POURED CONCRETE, WALL HEADER ONLY.OTHER OPENINGS | | (18-19) SPECIFY TYPE "L", WHICH IS FOR POURED CONCRETE. | | PLEASE ADDRESS.CHECK ALL OPENINGS. | | | | 2ND REVIEW, OPENINGS 18-19 STILL STATE THIS IS CBS, | | CONNECTION TYPE L.REVISE AND CHECK ALL OPENINGS. | | | | NEW COMMENT: | | | | ALL DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | FAC61G15-23.002 (WIND LOAD CHART).ENGINEERING IS NOT | | REQUIRED BUT IF YOU SUBMIT ENGINEERING, TWO SIGNED, | | SEALED, DATED ORIGINALS ARE REQUIRED. |
|