2007-06-13 16:01:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)ENGINEER IS TO SPECIFY ANCHORING OF TRACK INTO THE
 SPAN TUBE.THE INSTALLATION SCHEDULE STATES "NA", BUT
 THIS INFORMATION IS RQUIRED.PRODUCT APPROVAL DOES NOT
 ADDRESS ANCHORING INTO A METAL SUBSTRATE.
  
 2.)OPENINGS 8 THROUGH 17, INSTALLATION SCHEDULE
 SPECIFIES CBS, A FOR BOTTOM MOUNTING TYPE."A" IS
 POURED CONCRETE, WALL HEADER ONLY.OTHER OPENINGS
 (18-19) SPECIFY TYPE "L", WHICH IS FOR POURED CONCRETE.
 PLEASE ADDRESS.CHECK ALL OPENINGS.