2007-07-23 09:20:22DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. RESPONSE IS NOTED ON THE BADU JET SWIM PUMP BUT THE
 SYSTEM IS NOT CODE COMPLIANT PER THE FOLLOWING: A}
 FBC-2004 SEC.424.2.6.6.4, OR FBCR-2004 SEC.
 R4101.6.6.4 MINIMUM OF TWO SUCTION INLETS SHALL BE
 PROVIDED FOR EACH PUMP. SEPARATED BY A MINIMUM OF 3
 FEET OR LOCATED ON TWO DIFFERENT PLANES.B} FBC-2004
 SEC 424.2.6.6, OR FBCR-2004 SEC R4101.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. THE RESUBMITTED BADU
 SYSTEM DOES NOT REFLECT THOSE REQUIREMENTS. (DETAIL
 REQUIRED ON SHEET 4 OF 5 AND INDICATED ON 1 OF 5)
 NOTE: THE SUBMITTED BADU SYSTEM MATERIAL FROM MET
 LABORATORIES IS INDICATING THAT THE BADU JET SUCTION
 COVER HAS BEEN TESTED AND ACCEPTED BY A RECOGNIZED
 FACILITY AND COMPLIES WITH ANSI/ASME A112.19.8M BUT
 THIS SYSTEM IS NOT FBC-2004 CODE COMPLIANT.
  