Plan Review Notes
Plan Review Notes For Permit 07050661
Permit Number 07050661
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-06 14:48:58DENIED
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE SUBMIT A DETAIL OF THE PROPOSED "BADU SWIM
 JET". ALSO SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS OF THE PROPOSED "BADU SWIM JET" AND
 PLEASE PROVIDE THE FOLLOWING INFORMATION INDICATING THE
 SYSTEM IS CODE COMPLIANT.
 A} FBC-2004 SEC 424.2.6.6, OR FBCR-2004
 SEC R4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION INLETS. (DETAIL REQUIRED)
 B} FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 C} FBC-2004424.2.6.6.3, OR FBCR-2004
 SEC R4101.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE. (DETAIL REQUIRED)
 D} FBC-2004 SEC.424.2.6.6.4, OR
 FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF
 TWO SUCTION INLETS SHALL BE PROVIDED FOR
 EA PUMP. SEPARATED BY A MINIMUM OF 3
 FEET OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL REQUIRED)
 E} FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 NOTE: THE SUBMITTED VENT PIPE MAXIMUM LENGTH TABLE ON
 SHEET 3 ONLY GOES AS HIGH AS A 3 HORSEPOWER PUMP. FROM
 PAST PLAN REVIEWS OF THIS SYSTEM PUMPS HAVE HADHIGHER
 HORSEPOWER RATINGS. PLEASE ADJUST TABLE ACCORDINGLY FOR
 THE "BADU SWIM JET" SYSTEM ON THE RESUBMITTAL.
  
 2. SHEET 1 SPECIFICATIONS, PLEASE ADD THE "BADU SWIM
 JET" PUMP HORSEPOWER SIZE TO THE POOL EQUIPMENT ITEMS.
  
 3. SHEET 1 SPECIFICATIONS, PLEASE ADD THE THREE POOL
 RETURNS TO THE POOL EQIPMENT ITEMS. THE ONLY RETURNS TO
 POOL INDICATED ARE THE 3 JETS ON THE BENCH.
  
 END OF COMMENTS:
  