2007-06-06 14:48:58 | DENIED |
| REFERENCE: |
| ** FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING POOLS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PLEASE SUBMIT A DETAIL OF THE PROPOSED "BADU SWIM |
| JET". ALSO SUBMIT TWO COPIES OF MANUFACTURER'S |
| SPECIFICATIONS OF THE PROPOSED "BADU SWIM JET" AND |
| PLEASE PROVIDE THE FOLLOWING INFORMATION INDICATING THE |
| SYSTEM IS CODE COMPLIANT. |
| A} FBC-2004 SEC 424.2.6.6, OR FBCR-2004 |
| SEC R4101.6.6 ENTRAPMENT PROTECTION FOR |
| SUCTION INLETS. (DETAIL REQUIRED) |
| B} FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| C} FBC-2004424.2.6.6.3, OR FBCR-2004 |
| SEC R4101.6.6.3 (1,2,3) ENTRAPMENT |
| AVOIDANCE. (DETAIL REQUIRED) |
| D} FBC-2004 SEC.424.2.6.6.4, OR |
| FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF |
| TWO SUCTION INLETS SHALL BE PROVIDED FOR |
| EA PUMP. SEPARATED BY A MINIMUM OF 3 |
| FEET OR LOCATED ON TWO DIFFERENT PLANES. |
| (DETAIL REQUIRED) |
| E} FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. PLEASE |
| SUBMIT AN ENGINEERED TABLE FOR "VENT |
| PIPE MAXIMUM LENGTH" INDICATING PUMP |
| SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM |
| WHERE IT STARTS TO WHERE IT ENDS UP, |
| COMPLYING WITH THE THREE SECOND RELEASE. |
| NOTE: THE SUBMITTED VENT PIPE MAXIMUM LENGTH TABLE ON |
| SHEET 3 ONLY GOES AS HIGH AS A 3 HORSEPOWER PUMP. FROM |
| PAST PLAN REVIEWS OF THIS SYSTEM PUMPS HAVE HADHIGHER |
| HORSEPOWER RATINGS. PLEASE ADJUST TABLE ACCORDINGLY FOR |
| THE "BADU SWIM JET" SYSTEM ON THE RESUBMITTAL. |
| |
| 2. SHEET 1 SPECIFICATIONS, PLEASE ADD THE "BADU SWIM |
| JET" PUMP HORSEPOWER SIZE TO THE POOL EQUIPMENT ITEMS. |
| |
| 3. SHEET 1 SPECIFICATIONS, PLEASE ADD THE THREE POOL |
| RETURNS TO THE POOL EQIPMENT ITEMS. THE ONLY RETURNS TO |
| POOL INDICATED ARE THE 3 JETS ON THE BENCH. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |