2007-11-03 17:07:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW. THE COMMENT NUMBER SHALL
 REMAIN THE SAME AS 1ST REVIEW:
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND
 RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO
 STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO
 STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB.
 SECTION 102.2.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272,[email protected] OR CALVIN WILLIAMS,
 (561) 822-2284 [email protected]. THEIR FAX NUMBER IS
 (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION
 WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE
 SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE
 ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR
 INTERCEPTORS).
 ****RESPONSE NOTED, BUT THE GREASE INTERCEPTOR IS STILL
 SHOWN ON THE PLANS. ALSO IF THE GREASE INTERCEPTOR IS
 TO BE WAIVED, THEN AS REQUIRED A SAMPLE POINT SHALL BE
 INSTALLED ON THE GREASE LINE PRIOR TO CONNECTING INTO
 THE SANITARY DRAIN AND THE GREASE INTERCEPTOR SHOULD BE
 DELETED FROM THE RISER DIAGRAM.
  
 3. ALL SHEETS. THE ADDRESS OF THE ARCHITECT OF RECORD
 DOES NOT REFLECT THE ADDRESS RECORDED ON THE STATE OF
 FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE
 UPDATE THE DBPR WEBSITE OR THE TITLE BLOCKS ON EACH
 SHEET SO THE ADDRESS CORRELATES. FAC 61G1-16.004(1) &
 FS 481-2055.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED ON ALL
 SHEETS WITH THE ARCHITECT FIRM TITLE BLOCK. ALL SHEETS
 SHALL SHOW THE CORRECT ADDRESS.
  
 4. OK
 5. OK
  
 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN
 DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM.
 ****RESPONSE NOTED, BUT THE CODE ADOPTED IS NOT 2007
 BUILDING CODE. PLEASE CORRECT CODE REFERENCE.
  
 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE
 UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING
 AREA. SECTION 11-4.22.3.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. REMOVING
 THE TURNING AREA IS NOT A CORRECT RESPONSE TO SHOW
 COMPLIANCE. PLEASE SHOW THE REQUIRED TURNING AREA AND
 THE TOILET SHALL NOT BE IN THE TURNING AREA.
  
 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR
 PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE
 W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 &
 29.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR THE W/C:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 ___FOR THE LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN
 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND
 NONABSORBENT SURFACE.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT
 THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A
 PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER
 ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR
 THE BRANCH LINE TO THE BUILDING DRAIN . SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS
 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13). ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED.
  
 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE
 WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL
 EXPANSION CONTROL).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 REQUIREMENT FOR SECTION 503.1 IS A SHUT OFF VALVE FOR
 WATER HEATER. THE VALVE AS SHOWN WILL SHUT OFF MORE
 THAN THE WATER HEATER. THE PLACE OF DISPOSAL FOR THE
 T&P VALVE DISCHARGE LINE IS NOT INDICATED, NOR IS THE
 EMERGENCY PAN DRAIN LINE TERMINATION POINT.
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE
 PLANS.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 REFERENCE TO THE RPZV BACKFLOW IS FOUND ON SHT A-1.
  
 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY
 ADDRESSED. LENGTHS OF PIPE NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT
 INDICATED ON LEGEND.
  
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL
 CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC
 RISER DIAGRAM.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES
 INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING
 AS WELL AS THE BTU LOAD OF THE APPLIANCE.
  
 G. N/A
 H. N/A
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED.
  
 **********NEW COMMENTS***********
  
 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE
 SHOWN ON THE GAS RISER DIAGRAM.
  
 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS
 APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF
 VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE
 ACCESSIBLE PER SECTION 409.5.
  
 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]