2007-11-03 17:07:29 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW. THE COMMENT NUMBER SHALL |
| REMAIN THE SAME AS 1ST REVIEW: |
| |
| 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. |
| OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND |
| RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO |
| STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO |
| STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB. |
| SECTION 102.2.1. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| |
| 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY |
| ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| (561) 822-2272,[email protected] OR CALVIN WILLIAMS, |
| (561) 822-2284 [email protected]. THEIR FAX NUMBER IS |
| (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION |
| WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE |
| SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE |
| ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR |
| INTERCEPTORS). |
| ****RESPONSE NOTED, BUT THE GREASE INTERCEPTOR IS STILL |
| SHOWN ON THE PLANS. ALSO IF THE GREASE INTERCEPTOR IS |
| TO BE WAIVED, THEN AS REQUIRED A SAMPLE POINT SHALL BE |
| INSTALLED ON THE GREASE LINE PRIOR TO CONNECTING INTO |
| THE SANITARY DRAIN AND THE GREASE INTERCEPTOR SHOULD BE |
| DELETED FROM THE RISER DIAGRAM. |
| |
| 3. ALL SHEETS. THE ADDRESS OF THE ARCHITECT OF RECORD |
| DOES NOT REFLECT THE ADDRESS RECORDED ON THE STATE OF |
| FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE |
| UPDATE THE DBPR WEBSITE OR THE TITLE BLOCKS ON EACH |
| SHEET SO THE ADDRESS CORRELATES. FAC 61G1-16.004(1) & |
| FS 481-2055. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED ON ALL |
| SHEETS WITH THE ARCHITECT FIRM TITLE BLOCK. ALL SHEETS |
| SHALL SHOW THE CORRECT ADDRESS. |
| |
| 4. OK |
| 5. OK |
| |
| 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN |
| DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM. |
| ****RESPONSE NOTED, BUT THE CODE ADOPTED IS NOT 2007 |
| BUILDING CODE. PLEASE CORRECT CODE REFERENCE. |
| |
| 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE |
| UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING |
| AREA. SECTION 11-4.22.3. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. REMOVING |
| THE TURNING AREA IS NOT A CORRECT RESPONSE TO SHOW |
| COMPLIANCE. PLEASE SHOW THE REQUIRED TURNING AREA AND |
| THE TOILET SHALL NOT BE IN THE TURNING AREA. |
| |
| 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING |
| COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 |
| WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR |
| PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE |
| W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE |
| FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE |
| WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 & |
| 29. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW |
| COMPLIANCE WITH THE FOLLOWING: |
| ___FOR THE W/C: |
| A. 11-4.16.3 HEIGHT |
| B. 11-4.16.4 GRAB BARS |
| C. 11-4.16.5 FLUSH CONTROLS |
| D. 11-4.16.6 DISPENSERS |
| ___FOR THE LAV: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| B. 11-4.19.3 CLEAR FLOOR SPACE |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| D. 11-4.19.5 FAUCETS |
| E. 11-4.19.6 MIRRORS |
| |
| 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING |
| COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN |
| 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND |
| NONABSORBENT SURFACE. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| |
| 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT |
| THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A |
| PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER |
| ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT. |
| SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| |
| 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR |
| THE BRANCH LINE TO THE BUILDING DRAIN . SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| |
| 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, |
| VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS |
| 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13). ****RESPONSE |
| NOTED, BUT COMMENT NOT ADDRESSED. |
| |
| 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE |
| WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL |
| EXPANSION CONTROL). |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE |
| REQUIREMENT FOR SECTION 503.1 IS A SHUT OFF VALVE FOR |
| WATER HEATER. THE VALVE AS SHOWN WILL SHUT OFF MORE |
| THAN THE WATER HEATER. THE PLACE OF DISPOSAL FOR THE |
| T&P VALVE DISCHARGE LINE IS NOT INDICATED, NOR IS THE |
| EMERGENCY PAN DRAIN LINE TERMINATION POINT. |
| |
| 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE |
| PLANS. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO |
| REFERENCE TO THE RPZV BACKFLOW IS FOUND ON SHT A-1. |
| |
| 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY |
| ADDRESSED. LENGTHS OF PIPE NOT SHOWN. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE |
| NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT |
| INDICATED ON LEGEND. |
| |
| C. OK |
| |
| D. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL |
| CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC |
| RISER DIAGRAM. |
| |
| E. OK |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE |
| MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES |
| INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING |
| AS WELL AS THE BTU LOAD OF THE APPLIANCE. |
| |
| G. N/A |
| H. N/A |
| |
| I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED. |
| |
| **********NEW COMMENTS*********** |
| |
| 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE |
| SHOWN ON THE GAS RISER DIAGRAM. |
| |
| 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS |
| APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF |
| VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE |
| ACCESSIBLE PER SECTION 409.5. |
| |
| 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| NOTICE ONLY AT THIS TIME. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |