2007-11-05 11:18:01REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 NOTE: THERE WAS NO WRITTEN RESPONSE TO PREVIOUS
 MECHANICAL REVIEW COMMENTS IN THIS SUBMITTAL PACKAGE.
 PLANS WILL BE REVIEWED TO DETERMINE IF PREVIOUS
 COMMENTS WERE ADDRESSED.
  
 1. NOT ADDRESSED. INFORMATION IS STILL MISSING ON
 PLANS.
  
 2. NOT ADDRESSED.
  
 3. NO VENTILATION (OUTSIDE AIR) CALCULATIONS OR
 INFORMATION PROVIDED. OCCUPANCY AND OCCUPANT LOAD FOR
 PURPOSES OF VENTILATION SHALL BE DETERMINED IN
 ACCORDANCE WITH FBC,M TABLE 403.3 PROVIDE CALCULATIONS
 SHOWING OCCUPANCY, OCCUPANT LOAD, O.A. REQUIRED AND
 O.A. PROVIDED. ALSO, PROVIDE BATHROOM EXHAUST FAN
 INFORMATION ON EQUIPMENT SCHEDULE SHOWING MAKE/MODEL,
 CFM AND MEANS OF CONTROL. ALSO SHOW DISCHARGE LOCATION
 OF BATH EXHAUST IN ACCORDANCE WITH FBC,M 401.5. NOTE:
 BATH EXHAUST FAN IS NOT SHOWN ON ELECTRICAL PLANS. HOW
 WILL THIS FAN BE POWERED?
  
 4. AIR BALANCE SCHEDULE FOR THE SPACE HAS NOT BEEN
 PROVIDED. PLEASE READ PREVIOUS COMMENT AND PROVIDE ALL
 REQUESTED INFORMATION TO SHOW COMPLIANCE WITH THE CODE
 SECTIONS AS PREVIOUSLY REFERENCED. NOTE: IT IS
 PROHIBITED TO HAVE RETURN AIR IN THE KITCHEN FOR
 NON-DEDICATED KITCHEN HVAC SYSTEMS IN ACCORDANCE WITH
 FBC,M 407.1.
  
 5. NOT ADDRESSED. NO INFORMATION PROVIDED. SEE PREVIOUS
 REVIEW COMMENT.
  
 6. WITHOUT A WRITTEN RESPONSE, THE FOLLOWING IS NOTED
 BASED ON INFORMATION ON PLANS AND SUBMITTALS:
 A) PLAN INDICATES A/C IS NEW AND EXISTING. ONLY ONE
 SYSTEM IS SHOWN ON PLAN. ARE THERE TWO SYSTEMS? ONLY
 ONE IS LISTED ON EQUIPMENT SCHEDULE.
 B) FLOOR PLAN SHOWS A ?CU #5 ON ROOF.? IS THIS A
 ROOFTOP PACKAGE UNIT AS INDICATED BY EQUIPMENT SCHEDULE
 AND MANUAL J FORM OR A SPLIT SYSTEM WITH AHU AND CU? IS
 THIS THE NEW SYSTEM OR THE EXISTING SYSTEM?
 C) THE RTU LISTED ON PLAN DOES NOT MATCH THE RTU LISTED
 ON MANUAL J FORM.
 D) THE GAS RISER DIAGRAM SHOWS AN EXISTING 4 TON RTU ON
 ROOF. THIS DOES NOT MATCH ANY OF THE OTHER SUPPLIED
 INFORMATION. THERE IS ALSO A GAS LINE SHOWN GOING TO
 THE RTU FOR HEAT WHILE THE ELECTRICAL PLAN SHOWS A 5KW
 HEAT STRIP.
 E) ELECTRICAL PLAN SHOWS SERVICE FOR ONE AHU AND ONE CU
 FOR ONE SPLIT SYSTEM. WHERE IS THE 2ND SYSTEM ON
 ELECTRICAL PLANS? THE LETTER FROM A & J TECHNOLOGIES,
 INC. INDICATES THAT A NEW UNIT IS SIZED TO PROVIDE
 ADDITIONAL COOLING REQUIRED BY THE KITCHEN. IS THE ONE
 EXISTING SYSTEM BEING REPLACED OR IS THIS AN ADDITIONAL
 SYSTEM? IN ANY EVENT, THE ELECTRICAL SHOWS ONLY ONE
 SPLIT SYSTEM. THE ACTUAL NATURE OF THE WORK TO BE
 PERFORMED CAN NOT BE DETERMINED AT THIS TIME.
 F) THE LETTER INDICATES THAT A & J TECHNOLOGIES HAS
 DESIGNED THIS A/C SYSTEM. IN ORDER TO PERFORM DESIGN OF
 THIS COMMERCIAL SYSTEM, THEY ARE REQUIRED TO BE
 LICENSED AS AN ENGINEERING BUSINESS UNDER FS 471 OR AS
 A MECHANICAL CONTRACTOR UNDER FS 489. PROVIDE ALL
 RELEVANT LICENSE INFORMATION FOR THIS COMPANY. SEE FBC
 105.3.1.2(4).
  
 7. AIRFLOW ON SCHEDULE NOW SHOWS 1300 CFM, BUT WE STILL
 DON?T KNOW THE CFM OF THE 6 INCH DROP IN THE KITCHEN.
 THIS NEEDS TO BE ADJUSTED BASED ON WHAT EQUIPMENT IS
 ACTUALLY BEING USED AND WHAT IS REQUIRED BASED ON THE
 MANUAL J SUBMITTED.
  
 8. NOTE 9 HAS BEEN REMOVED. THERE IS NO LONGER A
 CONFLICT. HOWEVER, NOTE 4 NOW STATES 1\ INCH R-6 DUCT.
 GENERALLY 1 ? INCH IS REQUIRED TO ACHIEVE R-6. PLEASE
 CORRECT NOTE OR PROVIDE DUCT MANUFACTURER?S SUBMITTAL
 TO VERIFY THIS INFORMATION.
  
 9 AND 10. NO INFORMATION WAS PROVIDED REGARDING THE
 COMMERCIAL KITCHEN EXHAUST SYSTEM OTHER THAN A NOTE FOR
 CFM ON HE MANUAL J FORM. PROVIDE INFORMATION FOR A
 COMPLETE COMMERCIAL KITCHEN EXHAUST SYSTEM,
 DEMONSTRATING COMPLIANCE WITH FBC,M SECTIONS 505
 THROUGH 509.
  
 11. THIS COMMENT STILL STANDS AS SIGNIFICANT
 INFORMATION IS STILL MISSING.
  
 ENERGY CALCULATIONS: METHOD A COMPLIANCE FORM IS NOT
 AVAILABLE FOR THIS PROJECT AS THIS IS NOT A WHOLE
 BUILDING. SHOW COMPLIANCE WITH MINIMUM PRESCRIPTIVE
 REQUIREMENTS FOR ALL NEW COMPONENTS BEING INSTALLED IN
 ACCORDANCE WITH FBC 13-400.0.C.4.
  