Date |
Text |
2007-11-03 17:13:22 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY |
| ADDRESSED. LENGTHS OF PIPE NOT SHOWN. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE |
| NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT |
| INDICATED ON LEGEND. |
| |
| C. OK |
| |
| D. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL |
| CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC |
| RISER DIAGRAM. |
| |
| E. OK |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE |
| MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES |
| INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING |
| AS WELL AS THE BTU LOAD OF THE APPLIANCE. |
| |
| G. N/A |
| H. N/A |
| |
| I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED. |
| |
| **********NEW COMMENTS*********** |
| |
| 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE |
| SHOWN ON THE GAS RISER DIAGRAM. |
| |
| 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS |
| APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF |
| VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE |
| ACCESSIBLE PER SECTION 409.5. |
| |
| 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| NOTICE ONLY AT THIS TIME. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |