2007-10-06 18:39:51 | 2007-10-06 18:39:51 |
| |
| *** DENIED 2ND REVIEW *** |
| |
| 1) NOTE: PLEASE KNOW WITH RESPECT TO THE |
| DESIGNER/ENGINEER OF RECORD RESPONSE COMMENTS WHICH |
| SEEM TO CONTEST THIS REVIEWER NOTES. SEVERAL OF THE |
| ENGINEER RESPONSE NOTES MENTIONS PLANS DATED FEBRUARY |
| 07, HOWEVER THE PREVIOUS REVIEW WAS DONE ON PLANS |
| SUBMITTED WHICH WERE SIGNED, DATED AND SEALED ON |
| 3/19/07 BY THE ENGINEER OF RECORD. |
| PLEASE KNOW THAT THIS OFFICE/REVIEWER ONLY REVIEWS |
| THE PLANS WHICH ARE SUBMITTED WITH THE PERMIT |
| APPLICATION. |
| THE PLANS SUBMITTED FROM THE PREVIOUS REVIEW WERE |
| TURNED INTO THIS OFFICE WERE ALSO SUBMITTED BACK WITH |
| THIS RE-SUB AS OLD PLANS. |
| PLEASE SEE THE SIGNED, DATED AND SEALED PLANS DATED |
| 3/19/07 FROM THE ENGINEER WERE THE SAME PLANS |
| SUBMITTED. PLEASE CHECK THE PLANS SUBMITTED. |
| THE PREVIOUS COMMENTS WERE VALID BASED ON THE PLANS |
| SUBMITTED ON THE FIRST REVIEW AS SUBMITTED. |
| ** PLEASE SEE THOSE SAME PLANS HAVE HAD SEVERAL OF THE |
| PREVIOUS REVIEW COMMENTS *HIGH-LIGHTED*. |
| EXAMPLE: |
| A) PREVIOUS PLANS HAS 65AMP RATED CONDUCTORS ON 100AMP |
| DISCONNECTS W/70A OCP. |
| B) PREVIOUS PLANS HAVE 244AMPS OF LOAD SHOWN ON A |
| 300AMP PANEL BEING FED FROM A 100AMP DISCONNECT WITH |
| 70AMP FUSES. |
| C) PREVIOUS PLANS HAD EQUIPMENT/REFRIGERATOR AT FRONT |
| DOOR ON GENERAL PURPOSE CIRCUITS. |
| |
| ** THIS REVIEWER HAS STATED ON ALL REVIEWS PERFORMED BY |
| THIS OFFICE THAT IF THERE EVER ANY QUESTIONS, OR |
| COMMENTS TO PLEASE DO NOT HESITATE IN CONTACTING THIS |
| OFFICE/OR REVIEWER. AT THIS TIME WE MAY GO OVER |
| COMMENTS OR EVEN IF A MEETING IS NEEDED WE CAN SCHEDULE |
| A TIME TO GO OVER REVIEW COMMENTS. |
| |
| **THIS HAS NOT CHANGED, AND ONCE AGAIN IF THERE ARE ANY |
| ITEMS WHICH NEED TO BE GONE OVER PLEASE CALL. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2. PLEASE |
| SUBMIT LIGHTING PERFORMANCE CALCULATIONS. MAY NOT USE |
| METHOD *A* WHOLE BUILDING CALCULATION FOR THE TENANT |
| BUILD OUT. |
| PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER. PLEASE |
| SEE 13-415.2 AND TABLES. |
| PLEASE SEE LIGHTING CONTROLS STILL REQUIRED PER |
| 13-415.1.ABC.1.1, .1.2. PLEASE SEE THE ONLY DEVICE IS |
| THE OS SHOWN AT FRONT DOOR WHICH DOES NOT PROVIDE |
| NEEDED COVERAGE IN THE REAR OF SPACE. PLEASE ALSO SEE |
| THIS DOES NOT THE MEET THE REQUIREMENTS FOR SEPARATE |
| SPACE CONTROLS FOR AREAS WHICH HAVE FLOOR TO CEILING |
| HEIGHT PARTITIONS. |
| PLEASE ADJUST DEVICES, TIMES FOR DEVICES TO BE CHOSEN. |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3 WITH |
| RESPECT TO RISER AND TO BE SURE AND COORDINATE ALL WITH |
| THE ACTUAL EXISTING RISER. THE LAST SETS OF REVISED |
| ELECTRICAL PLANS SUBMITTED TO THE CITY FOR PERMITTING |
| AND REVISIONS INDICATES LARGER MAINS BEING TAPPED FORM |
| THE EXISTING MAIN AND GUTTER. |
| PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON THE |
| EXISTING SERVICE WITH NEW LOADS BEING ADDED.(LOAD |
| CALCULATIONS SUBMITTED, HOWEVER NOTE TO REMAIN DUE TO |
| KNOWN ADJUSTMENTS WHICH WILL BE NEEDED). |
| FOR EXAMPLE, ALL OTHER TENANT MAINS ARE SHOWN AT |
| 100AMPS, YET THERE IS ANOTHER RESTAURANT/ SANDWICH SHOP |
| WHICH HAS A LARGER SERVICE MAIN THAN 100AMPS. PLEASE |
| SEE 240, 310, 408, 230, 215.5, 220 ETC. PLEASE ADJUST |
| ALL. |
| FBC 106.3.5.1.2 |
| |
| 4) NOTE: PLEASE CLARIFY WATER HEATER LOAD AS THE NEW |
| CODE REQUIRED STORAGE TYPE WATER HEATER LOADS TO BE |
| SHOWN AT 125%. THESE ARE NOW CONSIDERED CONTINUOUS |
| LOADS. |
| PLEASE SEE 422.13 |
| |
| ** AS THERE WILL BE SEVERAL CHANGES, PLEASE BE SURE TO |
| GO OVER COMMENTS FROM ALL TRADES WHICH MAY AFFECT THE |
| SCOPE OF WORK ALONG WITH OTHER TRADE REVIEWED SHEETS. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |