Plan Review Notes
Plan Review Notes For Permit 07050622
Permit Number 07050622
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-06 18:39:512007-10-06 18:39:51
  
 *** DENIED 2ND REVIEW ***
  
 1) NOTE: PLEASE KNOW WITH RESPECT TO THE
 DESIGNER/ENGINEER OF RECORD RESPONSE COMMENTS WHICH
 SEEM TO CONTEST THIS REVIEWER NOTES. SEVERAL OF THE
 ENGINEER RESPONSE NOTES MENTIONS PLANS DATED FEBRUARY
 07, HOWEVER THE PREVIOUS REVIEW WAS DONE ON PLANS
 SUBMITTED WHICH WERE SIGNED, DATED AND SEALED ON
 3/19/07 BY THE ENGINEER OF RECORD.
 PLEASE KNOW THAT THIS OFFICE/REVIEWER ONLY REVIEWS
 THE PLANS WHICH ARE SUBMITTED WITH THE PERMIT
 APPLICATION.
 THE PLANS SUBMITTED FROM THE PREVIOUS REVIEW WERE
 TURNED INTO THIS OFFICE WERE ALSO SUBMITTED BACK WITH
 THIS RE-SUB AS OLD PLANS.
 PLEASE SEE THE SIGNED, DATED AND SEALED PLANS DATED
 3/19/07 FROM THE ENGINEER WERE THE SAME PLANS
 SUBMITTED. PLEASE CHECK THE PLANS SUBMITTED.
 THE PREVIOUS COMMENTS WERE VALID BASED ON THE PLANS
 SUBMITTED ON THE FIRST REVIEW AS SUBMITTED.
 ** PLEASE SEE THOSE SAME PLANS HAVE HAD SEVERAL OF THE
 PREVIOUS REVIEW COMMENTS *HIGH-LIGHTED*.
 EXAMPLE:
 A) PREVIOUS PLANS HAS 65AMP RATED CONDUCTORS ON 100AMP
 DISCONNECTS W/70A OCP.
 B) PREVIOUS PLANS HAVE 244AMPS OF LOAD SHOWN ON A
 300AMP PANEL BEING FED FROM A 100AMP DISCONNECT WITH
 70AMP FUSES.
 C) PREVIOUS PLANS HAD EQUIPMENT/REFRIGERATOR AT FRONT
 DOOR ON GENERAL PURPOSE CIRCUITS.
  
 ** THIS REVIEWER HAS STATED ON ALL REVIEWS PERFORMED BY
 THIS OFFICE THAT IF THERE EVER ANY QUESTIONS, OR
 COMMENTS TO PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE/OR REVIEWER. AT THIS TIME WE MAY GO OVER
 COMMENTS OR EVEN IF A MEETING IS NEEDED WE CAN SCHEDULE
 A TIME TO GO OVER REVIEW COMMENTS.
  
 **THIS HAS NOT CHANGED, AND ONCE AGAIN IF THERE ARE ANY
 ITEMS WHICH NEED TO BE GONE OVER PLEASE CALL.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2. PLEASE
 SUBMIT LIGHTING PERFORMANCE CALCULATIONS. MAY NOT USE
 METHOD *A* WHOLE BUILDING CALCULATION FOR THE TENANT
 BUILD OUT.
 PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER. PLEASE
 SEE 13-415.2 AND TABLES.
 PLEASE SEE LIGHTING CONTROLS STILL REQUIRED PER
 13-415.1.ABC.1.1, .1.2. PLEASE SEE THE ONLY DEVICE IS
 THE OS SHOWN AT FRONT DOOR WHICH DOES NOT PROVIDE
 NEEDED COVERAGE IN THE REAR OF SPACE. PLEASE ALSO SEE
 THIS DOES NOT THE MEET THE REQUIREMENTS FOR SEPARATE
 SPACE CONTROLS FOR AREAS WHICH HAVE FLOOR TO CEILING
 HEIGHT PARTITIONS.
 PLEASE ADJUST DEVICES, TIMES FOR DEVICES TO BE CHOSEN.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3 WITH
 RESPECT TO RISER AND TO BE SURE AND COORDINATE ALL WITH
 THE ACTUAL EXISTING RISER. THE LAST SETS OF REVISED
 ELECTRICAL PLANS SUBMITTED TO THE CITY FOR PERMITTING
 AND REVISIONS INDICATES LARGER MAINS BEING TAPPED FORM
 THE EXISTING MAIN AND GUTTER.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON THE
 EXISTING SERVICE WITH NEW LOADS BEING ADDED.(LOAD
 CALCULATIONS SUBMITTED, HOWEVER NOTE TO REMAIN DUE TO
 KNOWN ADJUSTMENTS WHICH WILL BE NEEDED).
 FOR EXAMPLE, ALL OTHER TENANT MAINS ARE SHOWN AT
 100AMPS, YET THERE IS ANOTHER RESTAURANT/ SANDWICH SHOP
 WHICH HAS A LARGER SERVICE MAIN THAN 100AMPS. PLEASE
 SEE 240, 310, 408, 230, 215.5, 220 ETC. PLEASE ADJUST
 ALL.
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE CLARIFY WATER HEATER LOAD AS THE NEW
 CODE REQUIRED STORAGE TYPE WATER HEATER LOADS TO BE
 SHOWN AT 125%. THESE ARE NOW CONSIDERED CONTINUOUS
 LOADS.
 PLEASE SEE 422.13
  
 ** AS THERE WILL BE SEVERAL CHANGES, PLEASE BE SURE TO
 GO OVER COMMENTS FROM ALL TRADES WHICH MAY AFFECT THE
 SCOPE OF WORK ALONG WITH OTHER TRADE REVIEWED SHEETS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]