Date |
Text |
2007-06-20 07:23:18 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. |
| OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND |
| RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO |
| STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO |
| STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB. |
| SECTION 102.2.1. |
| |
| 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY |
| ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| (561) 822-2272,[email protected] OR CALVIN WILLIAMS, |
| (561) 822-2284 [email protected]. THEIR FAX NUMBER IS |
| (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION |
| WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE |
| SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE |
| ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR |
| INTERCEPTORS). |
| |
| 3. ALL SHEETS. THE ADDRESS DOES NOT REFLECT THE ADDRESS |
| RECORDED ON THE STATE OF FLORIDA DBPR WEBSITE. (SEE |
| ATTACHED SHEET). PLEASE UPDATE THE DBPR WEBSITE OR THE |
| TITLE BLOCKS ON EACH SHEET SO THE ADDRESS CORRELATES. |
| FAC 61G1-16.004(1) & FS 481-2055. |
| |
| 4. SHT A-1 EQUIPMENT SCHEDULE ITEM K11 NOT SHOWN ON THE |
| FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 5. INDICATE THE OCCUPANCY LOAD AND SEATING ON THE |
| PLANS. SECTIONS 1004.3 & 1004.7. |
| |
| 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN |
| DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM. |
| |
| 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE |
| UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING |
| AREA. SECTION 11-4.22.3. |
| |
| 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING |
| COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 |
| WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR |
| PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE |
| W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE |
| FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE |
| WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 & |
| 29. |
| |
| 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING |
| COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN |
| 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND |
| NONABSORBENT SURFACE. |
| |
| 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT |
| THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A |
| PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER |
| ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT. |
| SECTION 106.1.1. |
| |
| 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR |
| THE BRANCH LINE TO THE BUILDING DRAIN . SECTION |
| 106.1.1. |
| |
| 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, |
| VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS |
| 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13). |
| |
| 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE |
| WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL |
| EXPANSION CONTROL). |
| |
| 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE |
| PLANS. |
| |
| 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. TYPE OF GAS, (LP OR NATURAL). |
| |
| D. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| E. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| G. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| H. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |