2007-06-20 07:23:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND
 RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO
 STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO
 STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB.
 SECTION 102.2.1.
  
 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272,[email protected] OR CALVIN WILLIAMS,
 (561) 822-2284 [email protected]. THEIR FAX NUMBER IS
 (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION
 WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE
 SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE
 ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR
 INTERCEPTORS).
  
 3. ALL SHEETS. THE ADDRESS DOES NOT REFLECT THE ADDRESS
 RECORDED ON THE STATE OF FLORIDA DBPR WEBSITE. (SEE
 ATTACHED SHEET). PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS ON EACH SHEET SO THE ADDRESS CORRELATES.
 FAC 61G1-16.004(1) & FS 481-2055.
  
 4. SHT A-1 EQUIPMENT SCHEDULE ITEM K11 NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.
  
 5. INDICATE THE OCCUPANCY LOAD AND SEATING ON THE
 PLANS. SECTIONS 1004.3 & 1004.7.
  
 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN
 DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM.
  
 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE
 UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING
 AREA. SECTION 11-4.22.3.
  
 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR
 PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE
 W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 &
 29.
  
 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN
 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND
 NONABSORBENT SURFACE.
  
 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT
 THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A
 PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER
 ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT.
 SECTION 106.1.1.
  
 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR
 THE BRANCH LINE TO THE BUILDING DRAIN . SECTION
 106.1.1.
  
 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS
 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13).
  
 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE
 WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL
 EXPANSION CONTROL).
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE
 PLANS.
  
 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]