Plan Review Notes
Plan Review Notes For Permit 07050622
Permit Number 07050622
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-16 11:44:25------------------DENIED--------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
  
 1. PLEASE SHOW SIZE OF OUTSIDE AIR DUCT FROM 12X12
 O.A.I. TO R/A PLENUM. ALSO, PLEASE SHOW CFM OF 6" DROP
 IN BACK OF SPACE. FBC 106.1.1.
  
 2. SUPPLY TRUNK LINE SHOWS ONE TRANSITION FROM 1/12 TO
 12/10. IS THE TRUNK LINE TO REMAIN THAT SIZE FOR THE
 REMAINING 3 DROPS? FBC 106.1.2.
  
 3.PLEASE SHOW VENTILATION CALCULATIONS WHICH
 DEMONSTRATE COMPLIANCE WITH FBC,M 403.3. ALSO, BATHROOM
 EXHAUST IS ALSO REQUIRED BY THIS SECTION. PLEASE SHOW
 MEANS OF EXHAUST, CFM AND DISCHARGE LOCATION.
  
 4. PLEASE SHOW AN AIR BALANCE SCHEDULE INCLUDING
 SUPPLY, RETURN, OUTSIDE AIR, BATHROOM EXHAUST, KITCHEN
 EXHAUST WITH MAKE-UP AIR TO SHOW PRESSURIZATION OF
 SPACE PER FBC 13-409.1.ABC.2 AND COMPLIANCE WITH
 KITCHEN SPACE REQUIREMENTS OF 13-409-1.ABC 3.6.1.
  
 5.PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2 (ALL SECTIONS) INCLUDING
 SECONDARY/AUXILIARY DRAIN PROTECTION PER 307.2.3.
  
 6. ELECTRICAL PLAN INDICATES A/C EQUIPMENT IS EXISTING,
 BUT SCOPE OF WORK AS DESCRIBED ON PERMIT APPLICATION
 STATES "SPACE IS CURRENTLY GUTTED."ALSO, HVAC NOTE #6
 SUGGESTS A/C EQUIPMENT IS NEW, NOT EXISTING. WHICH ONE
 IS CORRECT? FBC 106.1.1.
  
 7. EQUIPMENT SCHEDULE SHOWS INDOOR AIRFLOW AT 1000 CFM
 BUT FLOOR PLAN SHOWS 1300 CFM, NOT INCLUDING THE 6"
 DROP WHICH DOESN'T SHOW CFM. PLEASE SHOW CORRELATION
 BETWEEN SCHEDULE AND FLOOR PLAN.
  
 8. HVAC NOTE #4 IS IN CONFLICT WITH NOTE #9. PLEASE
 CLARIFY.
  
 9. SCOPE OF WORK ON PERMIT APPLICATION INDICATES GAS
 AND KITCHEN EQUIPMENT. PLEASE SHOW ALL VENTS AND
 KITCHEN EXHAUST PER FBC 106.3.5.1.4. ALSO, A COMMERCIAL
 KITCHEN GREASE EXHAUST VENTILATION SYSTEM W/ AUTOMATIC
 FIRE SUPPRESSION SYSTEM IS REQUIRED PER FBC,M 507.2.1
 AND 509.1.
  
 10. PLEASE SEE FBC,M 507.9 FOR CLEARANCE REQUIREMENTS
 RELATED TO TYPE I KITCHEN HOODS INCLUDING REQUIREMENTS
 FOR WALL SURFACES ADJASCENT TO THE HOOD AND COOKING
 EQUIPMENT.
  
 11. SIGNIFICANT INFORMATION IS MISSING FROM PLANS TO
 SHOW A CODE COMPLIANT BUILDING/SPACE AT THIS TIME.
 ADDITIONAL COMMENTS ARE POSSIBLE BASED ON THE
 ADDITIONAL INFORMATION WHEN IT IS PROVIDED.
  