Plan Review Notes
Plan Review Notes For Permit 07050622
Permit Number 07050622
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-08 08:20:10*** UNSAT ***
  
 1) NOTE:PLEASE STATE ALL OF THE RELEVANT CODES AS
 ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL
 SHEETS AS WELL AS ARCHITECTURAL.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101 (LS CODE).
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13 FOR COMPLIANCE FOR
 ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS
 13-415.1.AB1.1, 13-415.2.
 PLEASE SEE MISSING LIGHTING CONTROLS AS REQUIRED PER
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 ** AS NO INFORMATION ON SCHEDULING, TYPEOF DEVICES,
 FIXTURES, WATTAGES, OVER RIDES, ETC HAVE BEEN SUBMITTED
 FOR REVIEW, COMMENTS CAN NOT BE MADE AT THIS TIME.
  
 3) NOTE: PLEASE SEE THE SERVICE AS SHOWN CONTAINS A
 NOTE AT THE BOTTOM WHICH INDICATES *EXISTING* YET THE
 RISER AS SHOWN INDICATES SOME ITEMS AS *NEW*?? PLEASE
 CLARIFY ALL SERVICE EQUIPMENT AS SHOWN. PLEASE SEE THE
 PANEL SCHEDULE SHOWS THIS AS A 300AMP PANEL WITH 244
 AMP LOAD, YET THE PANEL IS ONLY BEING FED W/ A 2-POLE
 70AMP BREAKER WITH CONDUCTORS WHICH ARE ONLY RATED AT
 65AMPS??
 PLEASE SEE THE LOAD ON PANEL AS NOTED ABOVE SHOWN AT
 244AMPS, YET THE RISER LOAD CALCULATIONS ARE SHOWN
 SUBSTANTIALLY LESS FOR THIS SAME UNIT??
 PLEASE SEE THERE ARE SEVERAL ITEMS INCORRECT WITH THIS
 RISER AND NEW FEED TO PANEL.
 PLEASE SEE 240, 310, 408, 230, 215.5 ETC.
 PLEASE ADJUST ALL.
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE ALL BREAKERS ON THE PANEL SCHEDULE
 ARE 1-POLE BREAKERS? HOW IS THIS POSSIBLE FOR THE
 240/220/208 VOLT UNITS.
 IS ALL EQUIPMENT ON SINGLE POLE BREAKERS?
 PLEASE SEE NEC.
  
 5) NOTE: PLEASE SEE THE AHU SEEMS TO BE SHOWN WITH 10KW
 LOAD YET THE CONDUCTOR AND BREAKER SIZE IS NOT
 SUFFICIENT PER CODE.
 PLEASE SEE 240.4, 310.16, 424.3B.
  
 6) NOTE: PLEASE CLARIFY WATER HEATER AS PLANS INDICATES
 A STORAGE TYPE UNIT AND PANEL SCHEDULE INDICATES
 INSTANT TYPE HEATERS.
 PLEASE SEE 422.13 AND THE FOLLOWING COMMENT FOR LOAD
 CALCULATIONS.
  
 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON
 THE NEW PROPOSED LOAD FOR THIS TENANT SPACE AND FOR THE
 ENTIRE SERVICE FOR EXISTING LOADS AND NEW LOADS BEING
 ADDED TO SERVICE. THE LOAD AS SHOWN ON THE RISER LOAD
 CALCULATIONS IS NOT POSSIBLE.
 PLEASE SEE NEC 220 (ALL), 215.3, 230.42.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%
  
 8) NOTE: PLEASE SEE THE SHOW WINDOW RECEPTACLE IS BEING
 SHOWN ON THE GENERAL RECEPTACLE CIRCUIT WHICH IS NOT
 PERMITTED.
 210.62,220.14, 220.44.
  
 9) NOTE: PLEASE SEE THE PLANS INDICATE SOME SORT OF
 REFRIGERATOR AT THE FRONT ENTRANCE WHICH IS BEING SHOWN
 ON THE SAME GENERAL RECEPTACLE CIRCUIT AS SHOW WINDOW
 ETC. PLEASE SEE THE VA ON UNIT NEEDS TO BE VERIFIED AS
 THE CIRCUIT MOST LIKELY WILL NEED TO BE DEDICATED.
 PLEASE KNOW AS THE LOADS ARE NOT SHOWN, DETERMINATION
 CAN NOT BE DONE AT THIS TIME.
 PLEASE SEE 430, 422, 422, 220 ETC.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE 210.8B2 FOR ALL REQUIRED GFI
 PROTECTED CIRCUITS/RECEPTACLES ON PLANS IN KITCHEN FOOD
 PREP AREAS AND THE LIKE.
  
 11) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK IS TO
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC., EVEN IF ANY OF THESE ARE OWNER SUPPLIED. PLEASE
 SEE FBC 108.3.
  
 12) NOTE: PLEASE SEE CU IS BEING SHOWN ON 1-POLE
 CIRCUIT?
  
 13) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE
 SEE SOME ELECTRICAL ITEMS NOT SHOWING CIRCUITS. PLEASE
 ALSO SEE 700.12F FOR CIRCUITING OF EM/EXT LTS.
  
 14) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON
 PLANS/ TITLE BLOCKS.
 FAC 61G1-16.004 FBC 106.1.2
  
 15) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES
 SEVERAL ITEMS BEING EXISTING, HOWEVER AS THIS IS A NEW
 BUILD-OUT FROM PREVIOUS SHELL THIS IS NOT POSSIBLE.
 PLEASE ADJUST. 408.4.
 FBC 106.3.5.1.2
  
  
 ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION
 IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION
 CHANGES AND/OR PERMIT APPLICATION CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]