2007-06-08 08:20:10 | *** UNSAT *** |
| |
| 1) NOTE:PLEASE STATE ALL OF THE RELEVANT CODES AS |
| ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| 2006. |
| PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL |
| SHEETS AS WELL AS ARCHITECTURAL. |
| 2004 FBC W/2006 REVISIONS. |
| 2005 NFPA-70 (NEC). |
| 2003 NFPA-101 (LS CODE). |
| |
| 2) NOTE: PLEASE SEE FBC CHAPTER 13 FOR COMPLIANCE FOR |
| ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS |
| 13-415.1.AB1.1, 13-415.2. |
| PLEASE SEE MISSING LIGHTING CONTROLS AS REQUIRED PER |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| ** AS NO INFORMATION ON SCHEDULING, TYPEOF DEVICES, |
| FIXTURES, WATTAGES, OVER RIDES, ETC HAVE BEEN SUBMITTED |
| FOR REVIEW, COMMENTS CAN NOT BE MADE AT THIS TIME. |
| |
| 3) NOTE: PLEASE SEE THE SERVICE AS SHOWN CONTAINS A |
| NOTE AT THE BOTTOM WHICH INDICATES *EXISTING* YET THE |
| RISER AS SHOWN INDICATES SOME ITEMS AS *NEW*?? PLEASE |
| CLARIFY ALL SERVICE EQUIPMENT AS SHOWN. PLEASE SEE THE |
| PANEL SCHEDULE SHOWS THIS AS A 300AMP PANEL WITH 244 |
| AMP LOAD, YET THE PANEL IS ONLY BEING FED W/ A 2-POLE |
| 70AMP BREAKER WITH CONDUCTORS WHICH ARE ONLY RATED AT |
| 65AMPS?? |
| PLEASE SEE THE LOAD ON PANEL AS NOTED ABOVE SHOWN AT |
| 244AMPS, YET THE RISER LOAD CALCULATIONS ARE SHOWN |
| SUBSTANTIALLY LESS FOR THIS SAME UNIT?? |
| PLEASE SEE THERE ARE SEVERAL ITEMS INCORRECT WITH THIS |
| RISER AND NEW FEED TO PANEL. |
| PLEASE SEE 240, 310, 408, 230, 215.5 ETC. |
| PLEASE ADJUST ALL. |
| FBC 106.3.5.1.2 |
| |
| 4) NOTE: PLEASE SEE ALL BREAKERS ON THE PANEL SCHEDULE |
| ARE 1-POLE BREAKERS? HOW IS THIS POSSIBLE FOR THE |
| 240/220/208 VOLT UNITS. |
| IS ALL EQUIPMENT ON SINGLE POLE BREAKERS? |
| PLEASE SEE NEC. |
| |
| 5) NOTE: PLEASE SEE THE AHU SEEMS TO BE SHOWN WITH 10KW |
| LOAD YET THE CONDUCTOR AND BREAKER SIZE IS NOT |
| SUFFICIENT PER CODE. |
| PLEASE SEE 240.4, 310.16, 424.3B. |
| |
| 6) NOTE: PLEASE CLARIFY WATER HEATER AS PLANS INDICATES |
| A STORAGE TYPE UNIT AND PANEL SCHEDULE INDICATES |
| INSTANT TYPE HEATERS. |
| PLEASE SEE 422.13 AND THE FOLLOWING COMMENT FOR LOAD |
| CALCULATIONS. |
| |
| 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON |
| THE NEW PROPOSED LOAD FOR THIS TENANT SPACE AND FOR THE |
| ENTIRE SERVICE FOR EXISTING LOADS AND NEW LOADS BEING |
| ADDED TO SERVICE. THE LOAD AS SHOWN ON THE RISER LOAD |
| CALCULATIONS IS NOT POSSIBLE. |
| PLEASE SEE NEC 220 (ALL), 215.3, 230.42. |
| PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125% |
| |
| 8) NOTE: PLEASE SEE THE SHOW WINDOW RECEPTACLE IS BEING |
| SHOWN ON THE GENERAL RECEPTACLE CIRCUIT WHICH IS NOT |
| PERMITTED. |
| 210.62,220.14, 220.44. |
| |
| 9) NOTE: PLEASE SEE THE PLANS INDICATE SOME SORT OF |
| REFRIGERATOR AT THE FRONT ENTRANCE WHICH IS BEING SHOWN |
| ON THE SAME GENERAL RECEPTACLE CIRCUIT AS SHOW WINDOW |
| ETC. PLEASE SEE THE VA ON UNIT NEEDS TO BE VERIFIED AS |
| THE CIRCUIT MOST LIKELY WILL NEED TO BE DEDICATED. |
| PLEASE KNOW AS THE LOADS ARE NOT SHOWN, DETERMINATION |
| CAN NOT BE DONE AT THIS TIME. |
| PLEASE SEE 430, 422, 422, 220 ETC. |
| FBC 106.1.2 |
| |
| 10) NOTE: PLEASE SEE 210.8B2 FOR ALL REQUIRED GFI |
| PROTECTED CIRCUITS/RECEPTACLES ON PLANS IN KITCHEN FOOD |
| PREP AREAS AND THE LIKE. |
| |
| 11) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK IS TO |
| INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST |
| ETC., EVEN IF ANY OF THESE ARE OWNER SUPPLIED. PLEASE |
| SEE FBC 108.3. |
| |
| 12) NOTE: PLEASE SEE CU IS BEING SHOWN ON 1-POLE |
| CIRCUIT? |
| |
| 13) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE |
| SEE SOME ELECTRICAL ITEMS NOT SHOWING CIRCUITS. PLEASE |
| ALSO SEE 700.12F FOR CIRCUITING OF EM/EXT LTS. |
| |
| 14) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON |
| PLANS/ TITLE BLOCKS. |
| FAC 61G1-16.004 FBC 106.1.2 |
| |
| 15) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES |
| SEVERAL ITEMS BEING EXISTING, HOWEVER AS THIS IS A NEW |
| BUILD-OUT FROM PREVIOUS SHELL THIS IS NOT POSSIBLE. |
| PLEASE ADJUST. 408.4. |
| FBC 106.3.5.1.2 |
| |
| |
| ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION |
| IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION |
| CHANGES AND/OR PERMIT APPLICATION CHANGES. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |