Plan Review Notes
Plan Review Notes For Permit 07050620
Permit Number 07050620
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-08 07:28:38*** UNSAT ***
  
 1) NOTE:
 A) PLEASE SEE THE ADDRESS AS APPLIED IS FOR *SUITE
 #200*, HOW IS THIS POSSIBLE WHEN THE SCOPE OF WORK IS
 TO SERVICE THE BUILDING? THIS SHOULD NOT CONTAIN ANY
 SUITE/OR UNIT NUMBER.
 PLEASE CLARIFY SCOPE OF WORK AND PERMIT BEING APPLIED
 FOR ANY OTHER AREAS/UNITS/SUITES.
 PLEASE ALSO SEE THE OWNER INFORMATION AS STATED ON
 APPLICATION IS NOT CORRECT, PLEASE ADJUST OR PROVIDE
 INFORMATION ON OWNERSHIP.
  
 B) PLEASE SEE THE PERMIT APPLICATION MENTIONS THE WORK
 FOR A TRANSFER SWITCH ONLY WHICH WILL HAVE A *PORTABLE
 GENERATOR* UNIT. THIS IS BEING ASSUMED THE GENERATOR
 WILL BEONLY AT TIMES OF EMERGENCY YET THE PERMIT IS
 APPLIED FOR BY A GC?
 AS THE MAIN SCOPE OF WORK IS ELECTRICAL AND THE SLAB
 WORK IS MINOR IT SEEMS THIS SHOULD BE REVERSED BASED ON
 SCOPE AS SHOWN? THE PERMIT AS APPLIED SHOULD BE APPLIED
 FOR BY THE ELECTRICAL CONTRACTOR WITH THE GC SIGNED ON
 AS A SUB-CONTRACTOR FOR SLAB WORK. THIS WOULD BE AN
 *ELECTRICAL* PERMIT ONLY FOR ELECTRICAL CONTRACTOR AND
 *MISC* TYPE PERMIT FOR GC FOR CONCRETE WORK. AS
 APPLIED, INDICATES AT THIS TIME COMMERCIAL GENERATOR
 AND GENERATOR ELECTRICAL PERMIT.
 AS THE SCOPE OF WORK IS NOT CLEAR AT THIS TIME, THE
 REVIEW CAN ONLY BE BASED ON THE INFORMATION AS
 SUBMITTED ON PLANS AND PERMIT APPLICATION.
  
 2) NOTE: PLEASE STATE ALL OF THE RELEVANT CODES AS
 ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL
 SHEETS AS WELL AS ARCHITECTURAL.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2002 NFPA-110
  
 3) NOTE: PLEASE SEE THE SPECS/CUT SHEETS SUBMITTED SEEM
 TO INDICATE SOME KIND OF KEYED INTERLOCK AND THE PLANS
 CLEARLY STATE A MANUAL TRANSFER SWITCH (MTS). PLEASE
 CLARIFY AS THERE ARE SEVERAL *KEYED INTERLOCKS* ON THE
 MARKET WHICH DO NOT PROVIDE THE FAIL SAFE OR
 INADVERTENT MECHANICAL CONNECTION OF THE POWER ON THE
 NORMAL AND EMERGENCY SIDE. THIS JURISDICTION AND
 SEVERAL OTHERS HAVE FOUND MANY OF THESE TYPES OF
 DEVICES BEING SENT FROM THE MANUFACTURE WITH MORE THAN
 ONE KEY, MORE THAN ONE KEY AVAILABLE EITHER FROM THE
 MANUFACTURE OR THE LOCKING COMPANY WHICH COMPLETELY
 VOIDS ANY LISTING FOR INADVERTENT CONNECTION. AT THIS
 TIME BASED ON THE INFORMATION ANY KEYED INTERLOCK WHICH
 CAN BE TURNED IN THE *ON* POSITION AT THE SAME TIME OR
 ALLOWS MULTIPLE KEYS FROM NUMEROUS LOCATIONS CAN NO BE
 USED OR INSTALLED.
 702.6
 110.3, 90.7. PLEASE PROVIDE MORE INFORMATION ON THE MTS
 BEING INDICATED ON PLANS.
  
 4) NOTE: PLEASE PROVIDE NOTES FOR NEW SIGNAGE TO BE
 LOCATED AT BOTH LOCATIONS OF SERVICE EQUIPMENT. THE
 OLD/PREVIOUS SERVICE LOCATION AS THESE ARE NOW FEEDERS
 AND ARE CONSIDERED UNDER 225 AND NEW LOCATION AS THIS
 IS CONSIDERED THE NEW SERVICE LOCATION.
 230.2, 225.30-40.
  
 ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION
 IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION
 CHANGES AND/OR PERMIT APPLICATION CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-07 21:00:30NOTES TO FOLLOW ON 6/8