2008-11-13 12:05:22 | BUILDING PLAN REVIEW |
| PERMIT: 07050617 |
| ADD: 5405 BROADWAY |
| CONT: RAY GRAEVE & SONS CONST LLC |
| TEL: (561)432-5690 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 11-13-08 |
| REVIEW 3RD |
| ACTION: DENIED |
| |
| 1) --- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) OK. |
| |
| 3) THE PRODUCT APPROVALS SUBMITTED ARE MISSING THE |
| INSTALLATION REPORTS. WHEN RE-SUBMITTING, MATCH THE FL# |
| WITH THE CORRECT INSTALLATION REPORT. PROVIDE THE |
| PRODUCT APPROVAL FOR THE GLASS BLOCK AND NEW PRECAST |
| LINTEL, ALSO INDICATE THE SIZE OF THE LINTIL. IS IT 4", |
| 6", 8" OR 12". FBC 2104.1.5 THE MINIMUM LENGTH OF END |
| SUPPORT FOR LINTELS SHALL BE 4". INDICATE THE OPENING |
| DIMENTION. PLEASE CIRCLE OR HI-LIGHT WHICH SYSTEM WILL |
| BE USED FROM EACH PRODUCT. |
| |
| 4) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS. PROVIDE A WALL LEGEND INDICATING WHICH |
| WALLS ARE NEW AND WHICH WALLS ARE EXISTING. IN THE |
| LEGEND SHOW A DETAIL OF EACH TYPE OF WALL. SUBMIT AN |
| EXISTING AND A PROPOSED PLAN OF THE SPACE. |
| |
| 5) THE FOLLOWING INFORMATION REGARDING THE BUILDING IS |
| REQUIRED FOR REVIEW. |
| A) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 3. |
| B) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| TABLE 601. |
| C) SUBMIT A LIFE SAFETY PLAN SHOWING MEANS OF EGRESS |
| EXIT ACCESS ETC. |
| D) IF THERE IS AN AUTOMATIC SPRINKLER SYSTEM INSTALLED |
| IN THE BUILDING, PROVIDE THE NEW LAYOUT OF THE |
| SPRINKLER HEADS. THIS INFORMATION CAN BE SHOWN ON THE |
| NEW REFLECTED CEILING PLANS. FBC 106.3.5.1.1(5) |
| |
| ** NO RESPONSE NOT ADDRESSED** |
| 6) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE.. ARE THE INTERIOR WALLS CONCRETE BLOCK? |
| |
| 7) SEPARATE PERMITS ARE REQUIRED FOR THE FENCE AND |
| AWNINGS. WHEN APPLYING FOR THE PERMIT, SUBMIT THE |
| FOLLOWING INFORMATION. AWNINGS SHALL BE DESIGNED SO |
| THAT FABRIC OR MEMBRANE COVER CAN BE QUICKLY AND EASILY |
| REMOVED PER 3105.4.2.1 TIGHTLY WRAPED OR WOVEN CORDS |
| ARE ACCEPTABLE, WHEN 2 COPIES OF A DETAILED INSTRUCTION |
| GUIDE FOR REMOVAL ARE INCLUDED IN THE SUBMITTAL. IN |
| ADDITION 2 COPIES OF A NOTORIZED LETTER OF INTENT TO |
| REMOVE AT 75 MPH ARE REQUIRED. THE FENCE SHALL BE |
| DESIGNED THE MEET THE REQUIRED WIND LOADS OF THE CITY |
| OF WEST PALM BEACH WHICH IS 140 MPH. |
| |
| 8) THE ORDER AND ADJUDGED SECTION OF THE ZONING BOARD |
| OF APPEALS PAGE #7 D (V) STATES THAT ALL CHAIN-LINK |
| FENCES SHALL BE REMOVED; HOWEVER, THE SITE PLAN SHOWS A |
| 6? HIGH CHAIN LINK FENCE. CLARIFY. |
| |
| 9) THE LOCATION OF THE GAZEBO APPEARS TO BE REDUCING |
| THE ACCESSIBLE ROUTE TO THE BUILDING. ON SHEET #4 |
| INDICATE THE DIMENSION BETWEEN THE BUILDING AND THE |
| GAZEBO TO SHOW THE CLEAR WIDTH OF THE ACCESS ROUTE. THE |
| MINIMUM CLEAR WIDTH OF AN ACCESSIBLE ROUTE SHALL BE 36 |
| INCHES. IF A PERSON IN A WHEELCHAIR MUST MAKE A TURN |
| AROUND AN OBSTRUCTION, THE MINIMUM CLEAR WIDTH OF THE |
| ACCESSIBLE ROUTE SHALL BE AS SHOWN IN FIGURE 7(A) AND |
| FIGURE 7(B). 11-4.3.3 |
| |
| 10) A FINISH SCHEDULE SHALL BE SUBMITTED FOR THE DOOR |
| AND ROOM FINISHED. FBC 1210.2 WALLS WITHIN 2 FEET OF |
| URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE |
| FLOOR. SHOW COMPLIANCE. |
| |
| 11) SHEET #4. SUBMIT DETAIL INFORMATION FOR THE |
| STRUCTURAL FOUNDATION OF THE GAZEBO AND THE TRASH CAN |
| ENCLOSURE. ALSO STATE WHAT TYPE OF FASTENERS WILL BE |
| USED TO FASTEN THE TRASH CAN ENCLOSURE GATE TO THE |
| EXISTING BUILDING. ADDITIONAL INFORMATION REQUIRED |
| 106.1.2* |
| |
| 12) SUBMIT DETAIL DRAWING SHOWING ALL MATERIALS TO BE |
| USED FOR BLOCKING UP THE OPENINGS. THE PREVIOUS |
| DRAWINGS SHOWED GLASS BLOCK; IT IS NOT CLEAR WHAT TYPE |
| OF MATERIALS WILL BE USED ON THE NEW DRAWINGS. |
| ADDITIONAL INFORMATION REQUIRED. 106.1.2* |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| PHONE (561) 805-6726 |
| FAX (561)805-6676 |
| [email protected] |
| |
| |