Date |
Text |
2007-09-24 10:49:58 | ******UNSAT***** | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS | | BROADWAY AVENUE, DISPLAY/SHOW THE NUMERICAL ADDRESS. AS | | PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO | | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. | | SHOW ON SHEET 3 | | | | | | 7.BASED UPON THE ASSUMPTION THAT THIS STRUCTURE IS AN | | EXISTING BUSINESS OCCUPANCY, THE INTERIOR WALL AND | | CEILING MATERIALS SHALL BE CLASS A OR CLASS B IN EXITS | | AND EXIT ACCESS CORRIDORS, AND SHALL BE CLASS A, CLASS | | B, OR CLASS C IN ALL OTHER AREAS.BE SPECIFICFINISH | | FLOORING SHALL BE CLASS I OR CLASSII, NOT CLASS A AS | | INDICATED ON SHEET 3;NO MENTION OF THE WALL FINISH | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHEAL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|