Plan Review Notes
Plan Review Notes For Permit 07050617
Permit Number 07050617
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-18 12:59:08BUILDING PLAN REVIEW
 PERMIT: 07050617
 ADD: 5405 BROADWAY
 CONT: RAY GRAEVE & SONS CONST LLC
 TEL: (561)432-5690
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) F.S. 481.221 (2) ALL FINAL CONSTRUCTION DOCUMENTS
 AND INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS,
 PLANS SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY
 THE REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC
 RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE
 REGISTERED ARCHITECT WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE DATE ON WHICH THEY WERE SEALED. NOTE:
 ONE OF THE SHEET IS NOT SIGN OR DATED.
  
 3) THE PRODUCT APPROVALS SUBMITTED ARE MISSING THE
 INSTALLATION REPORTS. WHEN RE-SUBMITTING, MATCH THE FL#
 WITH THE CORRECT INSTALLATION REPORT. PROVIDE THE
 PRODUCT APPROVAL FOR THE GLASS BLOCK AND NEW PRECAST
 LINTEL, ALSO INDICATE THE SIZE OF THE LINTIL. IS IT
 4",6",8" OR 12". FBC 2104.1.5 THE MINIMUM LENGTH OF END
 SUPPORT FOR LINTELS SHALL BE 4". INDICATE THE OPENING
 DIMENTION.
  
 4) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS. PROVIDE A WALL LEGEND INDICATING WHICH
 WALLS ARE NEW AND WHICH ONES ARE EXISTING. IN THE
 LEGEND SHOW A DETAIL OF EACH TYPE OF WALL.
  
 5) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 6) STATE THE LEVEL OF ALTERATION IN ACCORDANCE WITH
 CH.3 OF THE 2004 EXISTING FBC. ARE THE INTERIOR WALLS
 CONCRETE BLOCK?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726