2007-06-11 17:19:04 | ******DENIED***** |
| |
| |
| 1.THE SUBMITTED PLANS DO NOT INDICATE WHAT THE |
| MODIFICATIONS TO THE EXISTING STRUCTURE ARE TO BE |
| CONDUCTED. |
| |
| 2.THE 2003 EDITION OF NFPA 101 AND THE 2004 EDITION |
| OF THE FLORIDA FIRE PREVENTION CODE SHALL BE |
| REFERENCED. |
| |
| 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| BE REMOVED FROM THE THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| BROADWAY AVENUE, DISPLAY/SHOW THE NUMERICAL ADDRESS. AS |
| PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO |
| LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| |
| 6.IF THE BUILDING OR PORTION OF THE BUILDING IS TO BE |
| OCCUPIED DURING THE SCOPE OF WORK, REQUIRED MEANS OF |
| EGRESS AND REQUIRED FIRE PROTECTION FEATURES SHALL BE |
| OPERATIONAL AND MAINTAINED. |
| |
| 7.BASED UPON THE ASSUMPTION THAT THIS STRUCTURE IS AN |
| EXISTING BUSINESS OCCUPANCY, THE INTERIOR WALL AND |
| CEILING MATERIALS SHALL BE CLASS A OR CLASS B IN EXITS |
| AND EXIT ACCESS CORRIDORS, AND SHALL BE CLASS A, CLASS |
| B, OR CLASS C IN ALL OTHER AREAS.BE SPECIFIC |
| |
| 8.PROVIDE LOCATION OF THE 2A:10BC RATED FIRE |
| EXTINGUISHER(S) SATISFYING THE 75' TRAVEL DISTANCE. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| |
| |