Plan Review Notes For Permit 07050617 |
Permit Number |
07050617 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-24 16:27:17 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT. | | | | 2} SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 2 | | FLUORESCENTS, AND NOTE THAT ALTHOUGH A MANUAL CONTROL | | IS LISTED, IT MUST AUTOMATICALLY TURN LIGHTS OFF WITHIN | | 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE PER | | 13-415.1ABC.1.2(A). DESIGNATE WHICH MANUFACTURER AND | | MODELS ARE BEING SPECIFIED FOR THIS PROJECT BY THE | | ENGINEER. | | | | 3} THE FIXTURE TYPES AND QUANTITIES ON THE MUST MATCH | | WHAT IS INDICATED ON THE ENERGY GAUGE SHEET #2 IN THE | | ENERGY CALCULATIONS. | | | | 4} SUBMIT FORMS WITH 13-415.2B OR 13-415.2.C.1 | | DENSITIES. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|