Plan Review Notes
Plan Review Notes For Permit 07050617
Permit Number 07050617
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-24 16:27:17 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 2
 FLUORESCENTS, AND NOTE THAT ALTHOUGH A MANUAL CONTROL
 IS LISTED, IT MUST AUTOMATICALLY TURN LIGHTS OFF WITHIN
 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE PER
 13-415.1ABC.1.2(A). DESIGNATE WHICH MANUFACTURER AND
 MODELS ARE BEING SPECIFIED FOR THIS PROJECT BY THE
 ENGINEER.
  
 3} THE FIXTURE TYPES AND QUANTITIES ON THE MUST MATCH
 WHAT IS INDICATED ON THE ENERGY GAUGE SHEET #2 IN THE
 ENERGY CALCULATIONS.
  
 4} SUBMIT FORMS WITH 13-415.2B OR 13-415.2.C.1
 DENSITIES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718