2007-06-26 16:04:27 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| COMMENTS FROM PREVIOUS LIST: |
| |
| 1.)THIS JOB DOES NOT FALL UNDER ANY OF THE EXCEPTIONS |
| TO ARCHITECTURE, FS481.229.THEREFORE, ALL PLANS |
| REQUIRED TO SHOW CODE COMPLIANCE ARE REQUIRED TO BE |
| PREPARED BY A DESIGN PROFESSIONAL. |
| |
| 2ND REVIEW; SITE PLAN NOT SEALED. |
| |
| 2-3.)ADDRESSED. |
| |
| 4.)THE ENGINEERING STATES THAT THIS IS A SINGLE |
| FAMILY HOME, BUILDING HEIGHT LESS THAN 60', OPEN |
| STRUCTURE, IMPORTANCE FACTOR OF .77.PLEASE REVISE |
| THESE NOTES TO BE SPECIFIC TO THIS JOB, WHICH IS A HIGH |
| RISE. |
| |
| 2ND REVIEW - HEIGHT AND IMPORTANCE FACTOR WERE NOT |
| REVISED AND PRESSURES APPEAR VERY LOW.THIS BUILDING |
| IS A HIGH RISE, AND AS SUCH THE GUARD SHACK IS SUBJECT |
| TO THE SAME PRESSURES AS THE BUILDING.NOTE THAT WIND |
| TUNNEL TEST REPORT MAY BE AVAILABLE. |
| |
| 5.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6 |
| (INCLUDE A OR B), BUILDING HEIGHT, SPRINKLER |
| INFORMATION, OCCUPANCY CLASSIFICATION FBC 3. |
| |
| 2ND REVIEW - THIS REFERS TO THE BUILDING.PROVIDE |
| BUILDING HEIGHT AS PRESSURE INFORMATION IS AFFECTED. |
| |
| 6.)SEE FBC603 REGARDING COMBUSTIBLES.SEE ALSO NOTES |
| 5 AND 6 ON SHEET 3 OF 3, ELITE PANELS, LIMITATIONS & |
| CONDITIONS OF USE.CODE REQUIREMENTS AND COMPLIANCE |
| ARE TO BE INCORPORATED INTO THE PLAN. |
| |
| 2ND REVIEW - THE RESPONSE STATES "OK".HOW IS THIS |
| ADDRESSED ON THE PLAN? |
| |
| 7.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED |
| FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| ORIGINALS (SITE PLAN). |
| |
| 8.)ADDRESSED. |
| |
| 9.)IF THIS IS A FULLY SPRINKLERED BUILDING, FIRE |
| SPRINKLERS WILL BE REQUIRED IN THIS NEW ROOM.FIRE |
| SPRINKLER PLANS ARE REQUIRED,FBC*106.3.5.1.1(5), |
| FS553.79 (2). |
| |
| 2ND REVIEW - IF THIS BUILDING WITHIN A FULLY |
| SPRINKLERED BUILIDING HAS A ROOF, FIRE SPRINKLER PLANS |
| (WITH THE NEW SPACE SPRINKLERED) REQUIRED. |
| |
| 10.)PROVIDE COMPONENT AND CLADDING DESIGN |
| INFORMATION, FBC1603.1.4. |
| |
| 2ND REVIEW - SEE OTHER COMMENTS; APPEARS LOW. |
| CLARIFY. |
| |
| 11.) PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD, FBC*106.3.3. |
| |
| 12.)THE PLAN STATES THAT THE GLASS IS TO BE IMPACT, |
| BUT NON IMPACT PRODUCT APPROVALS WERE SUBMITTED. PLEASE |
| ADDRESS.ALSO SEE ATTACHED POLICY, ITEM 13, REGARDING |
| USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS. |
| |
| 2ND REVIEW - STATES THAT NONHABITABLE SPACE DOES NOT |
| REQUIRED IMPACT PROTECTION.PLEASE REMOVE STATEMENT AS |
| THIS IS NOT A STANDALONE STRUCTURE UNDER ANY |
| EXCEPTIONS.IMPACT PROTECTOIN IS REQUIRED. |
| |
| 13.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| FOR THE ELITE PANEL, FAC9B72.THE PAPERWORK SUBMITTED |
| DOES NOT INCLUDE THE FLORIDA STATE PRODUCT APPROVAL. |
| |
| 2ND REVIEW - APPLICATION IS PENDING.PLEASE APPLY FOR |
| LOCAL PRODUCT APPROVAL; APPLICATION IS ATTACHED. |
| |
| 14.)A SIDE HINGE DOOR IS REQUIRED, FBC1001.1, |
| FBC1008.1.2 UNLESS THE SLIDING DOOR COMPLIES WITH |
| FBC1008.1.3.3. |
| |
| 15.)THIS WORK (DOOR AND WINDOW INSTALLATION) DOES NOT |
| FALL UNDER THE SCOPE OF WORK OF AN ALUMINUM SPECIALTIES |
| CONTRACTOR.NOTE THAT THIS IS A U LICENSE AND THE PALM |
| BEACH COUNTY WEBSITE IS UNAVAILABLE, SO I CANNOT |
| CONFIRM LICENSING AT THIS TIME. |
| |
| 2ND REVIEW - PLEASE COMPLETE ANOTHER PERMIT APPLICATION |
| AS A PORTION OF THE WORK IS TO BE PERMITTED WITH THE |
| ALUMINUM SPECIALTIES LICENSE AND A PORTION IS TO BE |
| PERMITTED WITH THE GLAZING LICENSE.TWO DIFFERENT |
| PERMIT NUMBERS WILL BE ISSUED. |
| |
| 16.)THE SITE PLAN IS TO BE PROVIDED IN A LEGIBLE |
| FORMAT, TO SCALE, FBC106.SHOW THE PROPOSED |
| IMPROVEMENT, TO SCALE, ON THE SITE PLAN.EXITING |
| INFORMATION, FBC10, SHOULD BE CLEAR ON THE SITE PLAN. |
| |
| |
| |