Plan Review Notes
Plan Review Notes For Permit 07050513
Permit Number 07050513
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-04 10:45:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THIS JOB DOES NOT FALL UNDER ANY OF THE EXCEPTIONS
 TO ARCHITECTURE, FS481.229.THEREFORE, ALL PLANS
 REQUIRED TO SHOW CODE COMPLIANCE ARE REQUIRED TO BE
 PREPARED BY A DESIGN PROFESSIONAL.
  
 2.)THE ENGINEERING TITLE FOR THIS JOB IS "SUN ROOM
 FOR :ONE WATERMARK PL".PLEASE REVISE TO BE
 CONSISTENT WITH THE SCOPE OF WORK.
  
 3.)THE ENGINEERING STATES THAT THIS IS EXPOSURE B.
 SEE FBC 1609.6.2.1(2), DEFINITION OF EXPOSURE C AND
 REVISE.
  
 4.)THE ENGINEERING STATES THAT THIS IS A SINGLE
 FAMILY HOME, BUILDING HEIGHT LESS THAN 60', OPEN
 STRUCTURE, IMPORTANCE FACTOR OF .77.PLEASE REVISE
 THESE NOTES TO BE SPECIFIC TO THIS JOB, WHICH IS A HIGH
 RISE.
  
 5.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6
 (INCLUDE A OR B), BUILDING HEIGHT, SPRINKLER
 INFORMATION, OCCUPANCY CLASSIFICATION FBC 3.
  
 6.)SEE FBC603 REGARDING COMBUSTIBLES.SEE ALSO NOTES
 5 AND 6 ON SHEET 3 OF 3, ELITE PANELS, LIMITATIONS &
 CONDITIONS OF USE.CODE REQUIREMENTS AND COMPLIANCE
 ARE TO BE INCORPORATED INTO THE PLAN.
  
 7.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS (SITE PLAN).
  
 8.)THE ENGINEERING STATES THAT THIS DESIGN IS FOR A
 4" SLAB, AND ALSO HAS A DISCLAIMER STATEMENT THAT
 DESIGN IS BASED ON INFORMATION PROVIDED BY CLIENT. THIS
 IS A HIGHRISE, THRESHOLD BUILDING.THE ENGINEER IS TO
 CONFIRM STRUCTURAL INFORMATION (PLANS ARE AVAILABLE FOR
 THIS BUILDING) FOR DESIGN.PLEASE DO SO AND REMOVE THE
 STATEMENT FROM THE PLAN.
  
 9.)IF THIS IS A FULLY SPRINKLERED BUILDING, FIRE
 SPRINKLERS WILL BE REQUIRED IN THIS NEW ROOM.FIRE
 SPRINKLER PLANS ARE REQUIRED,FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 10.)PROVIDE COMPONENT AND CLADDING DESIGN
 INFORMATION, FBC1603.1.4.
  
 11.) PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 12.)THE PLAN STATES THAT THE GLASS IS TO BE IMPACT,
 BUT NON IMPACT PRODUCT APPROVALS WERE SUBMITTED. PLEASE
 ADDRESS.ALSO SEE ATTACHED POLICY, ITEM 13, REGARDING
 USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS.
  
 13.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ELITE PANEL, FAC9B72.THE PAPERWORK SUBMITTED
 DOES NOT INCLUDE THE FLORIDA STATE PRODUCT APPROVAL.
  
 14.)A SIDE HINGE DOOR IS REQUIRED, FBC1001.1,
 FBC1008.1.2 UNLESS THE SLIDING DOOR COMPLIES WITH
 FBC1008.1.3.3.
  
 15.)THIS WORK (DOOR AND WINDOW INSTALLATION) DOES NOT
 FALL UNDER THE SCOPE OF WORK OF AN ALUMINUM SPECIALTIES
 CONTRACTOR.NOTE THAT THIS IS A U LICENSE AND THE PALM
 BEACH COUNTY WEBSITE IS UNAVAILABLE, SO I CANNOT
 CONFIRM LICENSING AT THIS TIME.
  
 16.)THE SITE PLAN IS TO BE PROVIDED IN A LEGIBLE
 FORMAT, TO SCALE, FBC106.SHOW THE PROPOSED
 IMPROVEMENT, TO SCALE, ON THE SITE PLAN.EXITING
 INFORMATION, FBC10, SHOULD BE CLEAR ON THE SITE PLAN.
  
  
  
  
  