2007-05-21 15:58:57 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE FEED TO SUB PANEL "B" MUST CONTAIN A #10CU
 EQUIPMENT GROUND PER 250.122.
  
 2} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B).
  
 3} THE "DINING ROOM" CIRCUIT MUST BE A 20 AMP AS
 INDICATED, BUT CANNOT BE ON WITH THE LIVING ROOM
 RECEPTACLES. SEE 210.52(B).
  
 4} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1).
  
 5} A RECEPTACLE IS REQUIRED AT THE REAR OF THE
 RESIDENCE PER 210.52(E).
  
 6} THE ENGINEER OF RECORD'S SEAL IS INDISCERNIBLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  