Date |
Text |
2007-06-24 14:14:48 | |
| |
| DENIED |
| |
| 1)DRAWING SHALL COMPLY WITH THE 2004 FBC W/ 2006 |
| AMENDMENTS |
| |
| 2)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4 |
| FBC |
| |
| 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, |
| AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE |
| INFORMATION. |
| |
| 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC* |
| |
| 5)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| ADDED TO THE PERMIT APPLICATION FEES |
| |
| NOTE: FEES ARE DUE IN THE AMOUNT OF $ 241.86 FOR THE |
| INCREASED VALUE AND STATE RADON FEE |
| |
| 6)DRAWINGS AND SURVEY SHALL SHOW THE LOCATION OF ALL |
| WORK, INCLUDING THE PROPOSED BUILDING(S) OR |
| STRUCTURE(S), IF THE NEW PATIOS /WALKS ARE IN THE SCOPE |
| OF WORK FOR THIS PERMIT THEY ARE REQUIRED TO BE SHOWN |
| ON THE SURVEY AND THE SIDE AND BACK SET MEASUREMENT ARE |
| REQUIRED TO MATCH ON THE SURVEY AND SITE DRAWING |
| |
| 7)TERMITE TREATMENT IS REQUIRED ON ALL EXTERIOR |
| CONCRETE WITHIN 1 FOOT OF PRIMARY STRUCTURE PER |
| 1816.1.6 OR R320.1.6 FBC DRAWINGS SHALL NOTE |
| |
| 8)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| DRAWINGS |
| |
| 9)SUBMIT ENERGY CALC'S PER 13-101.2.2 FBC. BE SURE |
| THAT THEY ARE SIGNED AND DATED BY PREPARER AND |
| OWNER/AGENT PRIOR TO SUBMITTAL |
| |
| 10)ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, |
| ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS |
| THEIR SEAL PER 61G15-23.002(2)FAC |
| |
| 11)AN ENGINEER PRACTICING THROUGH A DULY AUTHORIZED |
| ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND |
| LICENSE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| OF AUTHORIZATION # ON EACH SHEET PER |
| 61G15-23.002(2)FAC |
| |
| 12)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE. |
| THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG. |
| WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE |
| DENIED |
| |
| 13)PROVIDE PRODUCT APPROVAL FOR THE SIMPSON HURRICANE |
| STRAPS/TIES THAT ARE TO BE USED OR PROVIDE SCHEDULE |
| THAT LISTS THE CONNECTORS AND THEIR FLORIDA STATE |
| APPROVAL NUMBERS ON THE DRAWINGS |
| |
| 14)SHOW COMPLIANCE WITH R313.1.1 FBC RES FOR SMOKE |
| ALARMS |
| |
| 15)SHOWINSULATION R VALUE OF ADDITION ROOF THAT |
| MATCHES THE ENERGY CALC'S |
| |
| 16)PROVIDE THE MEAN ROOF HEIGHT AND BEAM ELEVATIONS |
| ON THE DRAWINGS |
| |
| 17)FOOTINGS SHALL BE PLACED A MIN OF 12" BELOW |
| FINISHED GRADE PER R403.1.4 FBC RES PLEASE NOTE DETAIL |
| 5/A4 |
| |
| 18)DRAWING DOES NOT SHOW CONTINUOUS BEAM AT ENTIRE |
| PERIMETER OR LINTEL ABOVE SGD IN THE GABLE END WALL |
| PLEASE CLARIFY. IF LINTEL IS USED PROVIDE LENGTHAND |
| PRODUCT APPROVAL |
| |
| 19)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE |
| OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2 |
| COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER |
| R401.4 FBC RES. |
| |
| 20)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO A PERMIT BEING |
| ISSUED |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |